SiBE04-401
4.18
Radiation Fin Temperature Rise
L4
Remote
Controller
Display
Method of
A radiation fin temperature rise is detected by checking the radiation fin thermistor with the
Malfunction
compressor on.
Detection
Malfunction
If the radiation fin temperature with the compressor on is above 90°C (100°C for (A)RK(X)H,
R(Y)N models).
Decision
Conditions
Supposed
Causes
Service Diagnosis
If a radiation fin temperature rise takes place 4 times successively, the system will be shut
down.
The error counter will reset itself if this or any other error does not occur during the following
60-minute compressor running time (total time).
Fin temperature rise due to defective outdoor unit fan
Fin temperature rise due to short-circuit
Fin thermistor defective
Connector in poor contact
Outdoor unit PCB defective
Troubleshooting
117