Daikin FTKS20CVMB Service Manual page 18

Inverter pair wall mounted type c-series
Hide thumbs Also See for FTKS20CVMB:
Table of Contents

Advertisement

SiBE04-401
Indoor Units
Models
Outdoor Units
Capacity
Rated (Min.~Max.)
Moisture Removal
Running Current (Rated)
Power Consumption
Rated (Min.~Max.)
Power Factor
COP (Rated)
Liquid
Piping
Gas
Connections
Drain
Heat Insulation
Indoor Units
Front Panel Color
Air Flow Rate m³/min
(cfm)
Type
Fan
Motor Output
Speed
Air Direction Control
Air Filter
Running Current (Rated)
Power Consumption (Rated)
Power Factor
Temperature Control
Dimensions (H×W×D)
Packaged Dimensions (W×D×H)
Weight
Gross Weight
Operation
H/M/L/SL
Sound
Sound Power H
Outdoor Units
Casing Color
Type
Compressor
Model
Motor Output
Type
Refrigerant
Oil
Charge
Type
Refrigerant
Charge
Air Flow Rate m³/min
(cfm)
Type
Fan
Motor Output
Running Current (Rated)
Power Consumption (Rated)
Power Factor
Starting Current
Dimensions (H×W×D)
Packaged Dimensions (W×D×H)
Weight
Gross Weight
Operation
H / L
Sound
Sound Power H
Drawing No.
Notes:
Specifications
ATKS20CVMB(9)
ARKS20CVMB
kW
2.0 (1.3~3.0)
Btu/h
6,800 (4,450~10,250)
kcal/h
1,720 (1,120~2,580)
L/h
0.9
A
2.8
W
500 (300~980)
%
79.6
W/W
4.00
φ
mm
6.4
φ
mm
9.5
φ
mm
18.0
Both Liquid and Gas Pipes
ATKS20CVMB(9)
White
H
7.7 (272)
M
5.9 (208)
L
4.2 (148)
SL
3.6 (127)
Cross Flow Fan
W
18
Steps
5 Steps, Silent and Auto
Right, Left, Horizontal and Downward
Removable / Washable / Mildew Proof Removable / Washable / Mildew Proof Removable / Washable / Mildew Proof
A
0.18
W
40
%
96.6
Microcomputer Control
mm
273×784×185
mm
834×325×258
kg
7.5
kg
11
dBA
38 / 32 / 25 / 22
dBA
56
ARKS20CVMB
Ivory White
Hermetically Sealed Swing Type
1YC23NXD#A
W
600
FVC50K
L
0.375
R410A
kg
0.80
H
34 (1,201)
L
24.8 (876)
Propeller
W
31
A
2.62
W
460
%
76.3
A
3.5
mm
550×765×285
mm
882×363×589
kg
30
kg
35
dBA
46 / 43
dBA
61
3D044248B
MAX. interunit piping length: 20m
MAX. interunit height difference: 15m
Amount of additional charge of refrigerant 20g/m for piping length exceeding 10m
The data are based on the conditions shown in the table below.
Cooling
Indoor ; 27°CDB/19°CWB
Outdoor ; 35°CDB/24°CWB
ATKS25CVMB(9)
ARKS25CVMB
2.5 (1.3~3.0)
8,550 (4,450~10,250)
2,150 (1,120~2,580)
1.2
3.9
695 (300~980)
79.3
3.60
φ
6.4
φ
9.5
φ
18.0
Both Liquid and Gas Pipes
ATKS25CVMB(9)
White
7.7 (272)
5.9 (208)
4.2 (148)
3.6 (127)
Cross Flow Fan
18
5 Steps, Silent and Auto
Right, Left, Horizontal and Downward
0.18
40
96.6
Microcomputer Control
273×784×185
834×325×258
7.5
11
38 / 32 / 25 / 22
56
ARKS25CVMB
Ivory White
Hermetically Sealed Swing Type
1YC23NXD#A
600
FVC50K
0.375
R410A
0.80
34 (1,201)
24.8 (876)
Propeller
31
3.72
655
76.6
4.4
550×765×285
882×363×589
30
35
46 / 43
61
3D044249B
Piping Length
7.5m
Specifications
230V, 50Hz
ATKS35CVMB(9)
ARKS35CVMB
3.4 (1.4~3.8)
11,600 (4,750~12,950)
2,920 (1,200~3,270)
1.9
4.9
1,060 (300~1,300)
94.3
3.21
φ
6.4
φ
9.5
φ
18.0
Both Liquid and Gas Pipes
ATKS35CVMB(9)
White
7.7 (272)
6.1 (215)
4.4 (155)
3.8 (134)
Cross Flow Fan
18
5 Steps, Silent and Auto
Right, Left, Horizontal and Downward
0.18
40
96.6
Microcomputer Control
273×784×185
834×325×258
7.5
11
39 / 33 / 26 / 23
57
ARKS35CVMB
Ivory White
Hermetically Sealed Swing Type
1YC23NXD#A
600
FVC50K
0.375
R410A
1.00
31.3 (1,105)
22.4 (791)
Propeller
35
4.72
1,020
94.0
5.4
550×765×285
882×363×589
32
38
47 / 44
62
3D044250B
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
9