(29)Multi-Function Analog Input Function Selection
•The settings and functions for the multi-function analog input (terminal AUX) are
listed in Table 15.
Table 15
Function
Setting
Auxiliary frequency command Auxilary Freq.Cmd. (Max. output frequency)
00
Frequency command
01
gain (FGAIN)
Frequency command
02
bias 1 (FBIAS1)
Frequency command
03
bias 2 (FBIAS2)
Overtorque
04
detection level
05
Output frequency bias (VBIAS)
06
Scaling of ACC/DEC time(TK)
DC injection braking
07
Stall prevention level
08
during running
PID control reference
09
input
Frequency command
10
lower limit
Jump frequency setting4
11
RS-485 communication
12
application
Multi-function analog input function list
LCD Display
Description (100% output corresponds to 10 V level)
Total gain= Bn-05 ×FGAIN
∼Freq. Cmd.Gain
(Frequency command in voltage form, terminal VIN
frequency command)
Cmd. Bias 1
Total bias= Bn-06 + FBIAS1
Cmd. Bias 2
Total bias= Bn-06 + FBIAS2
According to analog input voltage (0∼10V), change
Over Tq. Level
overtorque detection level (setting of Cn-32 is disabled)
Output Voltage
Total output voltage= V/F pattern voltage + VBIAS
Acc&Dec Coeff Real ACC/DEC time= ACC/DEC time (Bn-0~24) / TK
According to analog input voltage (0∼10V), change
the level of DC injection current (0-100%).
DC Brakin current
(inverter rated current=100%, the setting of DC
injection current Cn-15 is disabled )
According to analog input voltage (1.5V∼10V), change
Run Still Level
the level of stall prevention during running (30%∼200%)
(inverter rated current=100%, the setting Cn-26 is disabled.)
Multi-function analog input (terminal AUX) used as
PID Command
PID control reference input (0~10V). Please refer to
"PID CONTROL BLOCK DIAGRAM" on page 42.
Change the frequency command lower-limit (0-100%)
value according to the then analog input voltage (0~10V)
(Max. output frequency (Cn-02) corresponds to the
Freq. Cmd. Low Bound
100% analog output. The actual lower-limit is
determined by the maximum of Cn-19 and the value
corresponding to the multi-function analog input
terminal).
Set the jump frequency 4, according to analog input
Freq Jump 4
voltage (0~10V), while Cn-20~Cn-23 can be used to set
the jump frequency 1~3 and their jump frequency width.
The analog value of AUX (0-1024/0-10V) can be read
Comm. Control
through RS-485 communication.
87
(Sn-29)