■ AC reactor
• An AC reactor can be added on the power supply side if the inverter is
connected to a much larger capacity power supply system, or the inverter is
within short distance (<10m) from power supply systems, or to increase the
power factor on the power supply side.
• Choose the proper AC reactor according to the below list.
V
220V
1 φ /3 φ
220V
3 φ
440V
3 φ
Note: The AC reactors are applied only to input side. Do not apply it to output side.
Table 5 AC reactor list
Inverter Model
Rated
HP
current
1
4.8A
2
6.5A
3
9.6A
5.4
17.5A
7.5
24A
10
32A
15
48A
20
64A
1
2.6A
2
4A
3
4.8A
5.4
8.7A
7.5
12A
10
15A
15
24A
20
32A
AC reactor
Code No.
3M200D1610021
3M200D1610030
3M200D1610048
3M200D1610056
3M200D1610064
3M200D1610072
3M200D1610081
3M200D1610099
3M200D1610137
3M200D1610145
3M200D1610153
3M200D1610161
3M200D1610170
3M200D1610188
3M200D1610196
3M200D1610200
23
Specification
(mH/A)
2.1mH/5A
1.1mH/10A
0.71mH/15A
0.53mH/20A
0.35mH/30A
0.265mH/40A
0.18mH/60A
0.13mH/80A
8.4mH/3A
4.2mH/5A
3.6mH/7.5A
2.2mH/10A
1.42mH/15A
1.06mH/20A
0.7mH/30A
0.53mH/40A