Sensor-Specifi C Menus; Flow - Signet 9900 Operating Instructions Manual

Table of Contents

Advertisement

Sensor-Specifi c Menus
The following pages list the sensor-specifi c settings for each sensor type.

Flow

This is the normal display
and does not time out.
VIEW Mode Menu
Display the fl ow rate and the resettable totalizer. Press ► to reset the totalizer. (If Reset is locked, enter
the password fi rst.) Lock or Unlock the totalizer in the OPTIONS menu.
This is the resettable totalizer View display.
Display the Permanent Totalizer value (note the "P" indicating Permanent).
Pressing ► displays units of measure.
Displays the 4 to 20 mA LOOP output.
Bottom line shows one of three states (OFF, ON, PLS) for each of the three relays.
Displays remaining time for CYC LOW or CYC HIGH mode. The relay(s) will remain ON while counting down.
NOTE: (Reset the Timer) In the RELAY menu, select TEST RELAY function.
The timer will reset to 0 if the condition no longer exists when the TEST is performed.
The timer will restart if the condition still exists.
CAL Menu
YES prevents relays from activating while making adjustments, and relays in PULSE mode will suspend
pulsing. Output is held until the user exits the CAL menu. Select YES/NO.
Default = NO.
Set K-Factor (pulses per unit volume) from Flow Sensor manual.
Min: 0.0001, max 999999. Cannot be zero. Default = 60.0000.
Sets the volume of each count of the Totalizer as a multiple of the volume unit of the K-Factor.
Min: 0.0001, max 999999. Cannot be zero. Default = 1.0000.
Select to calibrate using Rate method (see Appendix).
Select to calibrate using Volume method (see Appendix).
Enter date of calibration (mm-dd-yyyy) and initials of calibrator (ii).
FLOW Setup Checklist
1. Make sure FLOW sensor type is selected
(see System Setup Menu, page 25).
2. Set the Units of Measurement.
3. Set Sensor Type (Freq or S
4. If LOOP is used, set the minimum and maximum 4 to 20 mA setpoints.
5. Set K-Factor (pulses per Unit Volume) from Flow Sensor manual.
6. Set Totalizer factor.
7. Set Last Cal Date and initials.
8. If desired, set up relay functions for your own application.
L).
3
9900 Transmitter
31