Sensor Wiring
Wiring for:
2250
2551*
* 2551-XX-21, -41
Display Magmeter
Wiring for:
8058-1
8058-1
4-20 mA to S
close-up
8058-2
14
9900 Transmitter
2350
2450
2750/2751
2850
NOTE: The 2850 has no SHIELD wire.
+GF+
Signet 8058 i-Go™
4-20 mA to S
3
L Converter
4-20 mA input
S
3
L Output
Signet 8058 i-Go™
3
L Converter
3
S
L Output
8058-2
close-up
9900 S
3
L Inputs
Black
Red
White
Shield
9900 S
3
L Inputs
Black
Red
White
Shield
3
9900 S
L Inputs
3
S L
DATA
N/C
7 8 9
WHITE
RED
BLACK
Technical Notes:
• Use three conductor shielded
cable for sensor cable splices
up to 305 m (1000 ft) max.
• Maintain cable shield through
cable splice.
• Route sensor cable away
from AC power lines.
• Connect the silver (shield)
wire to earth ground in case
of EMI noise interference.
Technical Notes:
• The 2850 has no SHIELD wire.
• To work correctly with the
9900, the 2850 must be set
for the custom cell constant or
the actual probe cell constant
and the 9900 set for a 1.0 cell
constant.
Technical Notes:
• The cable length from the
8058 to the 9900 must not
exceed 60 m (200 ft).
• When using the 8058-2,
connect the loop source to
Channel 1 input ONLY.
• See the 8058 manual for
more information.