Vega PULS SR 68 Quick Setup Manual page 18

Table of Contents

Advertisement

5 Set up the sensor with the display and adjustment module
The menu item "Delete" is used to completely delete an already cre-
ated false signal suppression. This is useful if the saved false signal
suppression no longer matches the metrological conditions in the
vessel.
The menu item "Extend" is used to extend an already created false
signal suppression. This is useful if a false signal suppression was
carried out with a too high level and not all false signals could be de-
tected. When selecting "Extend", the distance to the product surface
of the created false signal suppression is displayed. This value can
now be changed and the false signal suppression can be extended to
this range.
VEGAPULS SR 68 • Modbus and Levelmaster protocol
18

Advertisement

Table of Contents
loading

Table of Contents