Thermostat Control - Daikin FLKS25BAVMB Service Manual

Inverter pair floor/ceiling suspended dual type ba series
Hide thumbs Also See for FLKS25BAVMB:
Table of Contents

Advertisement

Main Functions
1.7

Thermostat Control

Thermostat control is based on the difference between the room thermistor temperature and the
target temperature.
Thermostat OFF Condition
Š The temperature difference is in the zone A.
Thermostat ON Condition
Š The temperature difference returns to the zone C after being in the zone A.
Š The system resumes from defrost control in any zones except A.
Š The operation turns on in any zones except A.
Š The monitoring time has passed while the temperature difference is in the zone B.
Cooling / Dry
Heating
Refer to "Temperature Control" on page 22 for detail.
28
(Cooling / Dry : 10 minutes, Heating : 10 seconds)
C
–1.5°C
B B
A
OFF
OFF
OFF
A
B
1.0°C
C
Room thermistor temperature – target temperature
ON
Cooling : –1.0°C
Dry : –1.0°C
Cooling : –2.0°C
Dry : –2.5 ~ –2.0°C
Room thermistor temperature – target temperature
1.5°C
0.5°C
ON
ON
SiENBE05-722_A
(R12391)
(R12392)
Function and Control