3.19 Thermistor or Related Abnormality (Outdoor Unit)

H9, J3, J6, P4
Remote Control
Display
Method of
This fault is identified based on the thermistor input voltage to the microcomputer.
Malfunction
A thermistor fault is identified based on the temperature sensed by each thermistor.
Detection
„ The thermistor input voltage is above 4.96 V or below 0.04 V with the power on.
Malfunction
„ J3 error is judged if the discharge pipe temperature is lower than the heat exchanger
Decision
Conditions
„ Disconnection of the connector for the thermistor
Supposed
„ Defective thermistor
Causes
„ Defective heat exchanger thermistor in the case of J3 error (outdoor heat exchanger
„ Defective outdoor unit PCB
„ Defective indoor unit PCB
Service Diagnosis
temperature.
thermistor in cooling operation, or indoor heat exchanger thermistor in heating operation)
Troubleshooting
89