Check
4.1.4 Installation Condition Check
Check No.07
4.1.5 Discharge Pressure Check
Check No.08
106
Installation condition check
Check the
allowable dimensions of the
air suction and discharge
area.
Normal
Is the discharged air
short-circuited?
NO
Is the outdoor
heat exchanger very dirty?
NO
Is the
airflow blocked by
obstacles or winds blowing
in the opposite direction?
NO
Discharge pressure check
High?
YES
Is the stop valve open?
YES
Is the connection pipe
deformed?
NO
Is the air filter or
indoor / outdoor heat exchanger
dirty?
Not dirty
Abnormal
YES
YES
YES
NO
NO
YES
Dirty
SiENBE05-722_A
Change the installation
location or direction.
Change the installation
location or direction.
Clean the outdoor heat
exchanger.
Change the installation
location or direction.
Check the outdoor temperature.
(The outdoor temperature
should be 46°C or lower.)
(R9459)
Replace the compressor.
Open the stop valve.
Replace the pipe installed at
the site.
Clean the dirty one.
Replace the compressor.
(R11718)
Service Diagnosis