Specifications

Attribute
Voltage and current ratings
Isolation voltage
Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
Temperature, surrounding air, max
Enclosure type rating
Torque
Dimensions (HxWxD), approx
Wire size
North American temperature code
ATEX temperature code
IECEx temperature code
Attribute
Voltage and current ratings
Isolation voltage
Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
Temperature, surrounding air, max
Enclosure type rating
Torque
Dimensions (HxWxD), approx
Wire size
North American temperature code
ATEX temperature code
IECEx temperature code
10
1756-PA72
1756-PA75
Input: 120/240V
Input:
AC, 50/60 Hz,
120/240V AC,
100VA, 100 W
50/60 Hz, 100VA,
100 W
Output: 2.8 A,
24V DC; 10 A,
Output: 2.8 A,
5.1V DC; 4 A,
24V DC; 13 A,
3.3V DC; 1.5 A,
5.1V DC; 4 A,
1.2V DC; 75 W max,
3.3V DC; 1.5 A,
20 A inrush max
1.2V DC; 75 W max,
20 A inrush max
250V (continuous), Reinforced Insulation Type, Power Input to Backplane
0 °C < Ta < +60 °C (+32 °F < Ta < 140 °F)
60 °C (140 °F)
None (open-style)
0.8 N•m (7 lb•in)
14.0 x 11.2 x 14.5 cm (5.51 x 4.41 x 5.71 in.)
2.5 mm² (14 AWG) solid or stranded copper wire rated at 90 °C (194 °F), or greater, 1.2 mm (3/64 in.) insulation max
T4
-
-
1756-PA50
Input: 120/240V AC, 50/60 Hz, 81 W (90VA), 50 °C (122 °F),
68 W (77VA), 60 °C (140 °F)
Output: 2.5 A, 24V DC; 8 A, 5.1V DC; 2 A, 3.3V DC; 1.5 A, 1.2V DC;
50 °C (122 °F), 60 W max; 60 °C (140 °F), 50 W max; 20 A inrush
max
250V (continuous), Reinforced Insulation Type, Power Input to Backplane
0 °C < Ta < +60 °C (+32 °F < Ta < +140 °F)
60 °C (140 °F)
None (open-style)
0.8 N•m (7 lb•in)
14.0 x 7.8 x 14.5 cm (5.51 x 3.07 x 5.71 in.)
2.5 mm² (14 AWG) solid or stranded copper wire rated at 90 °C (194 °F), or greater, 1.2 mm (3/64 in.) insulation max
T4
-
-
Rockwell Automation Publication 1756-IN619A-EN-P - April 2016
1756-PB72,
1756-PB75,
1756-PB72K
1756-PB75K
Input: 24V DC,
Input: 24V DC,
95 W
95 W
Output: 2.8 A,
Output: 2.8 A,
24V DC; 10 A,
24V DC; 13 A,
5.1V DC; 4 A,
5.1V DC; 4 A,
3.3V DC; 1.5A,
3.3V DC; 1.5 A,
1.2V DC; 75 W max,
1.2V DC; 75 W max,
30 A inrush max
30 A inrush max
T4
T4
1756-PB50
Input: 24V DC; 50 °C (122 °F), 85 W; 60 °C (140 °F), 70 W
Output: 2.5 A, 24V DC; 8 A, 5.1V DC; 2 A, 3.3V DC; 1.5 A, 1.2V DC;
50 °C (122 °F), 60 W max; 60 °C (140 °F), 50 W; 20 A inrush max
T4
T4
1756-PC75
1756-PH75
Input: 48V DC,
Input: 125V DC,
95 W
95 W
Output: 2.8 A,
Output: 2.8 A,
24V DC; 13 A,
24V DC; 13 A,
5.1V DC; 4 A,
5.1V DC; 4 A,
3.3V DC; 1.5 A,
3.3V DC; 1.5 A,
1.2V DC; 75 W max,
1.2V DC; 75 W max,
30 A inrush max
30 A inrush max
-
-