Specifications - Allen-Bradley 1769-PA2K Installation Instructions Manual

Compact i/o expansion power supplies
Table of Contents

Advertisement

Specifications

Technical Specifications
Attribute
Input voltage range
Input frequency range
Power supply distance
(1)
rating
Operating altitude
Isolation voltage
Power consumption
Power dissipation
Current capacity @ 5V DC
Current capacity @ 24V DC
Inrush current, max
Fuse type
Dimensions (HxWxD),
approx
Weight, approx
(2)
Wiring category
Wire size
North American temp
code
ATEX/IEC temp code
Enclosure type rating
(1) You can use a maximum of two banks of I/O modules. This condition occurs when configuring your system with a MicroLogix 1500 controller, one
expansion cable, one expansion power supply, and a total of eight I/O modules. The expansion power supply cannot be directly connected to the
MicroLogix 1500 controller.
(2) Use this Conductor Category information for to plan conductor routing. See the Industrial Automation Wiring and Grounding Guidelines,
publication 1770-4.1.
(3) Catalog numbers followed by a "K" indicate a conformal coating option.
(3)
1769-PA2, 1769-PA2K
1769-PB2, 1769-PB2K
85...265V AC
19.2...31.2V DC
47...63 Hz
N/A
8
8 I/O modules can be connected on either side of the power supply for a maximum of 16 modules
2000 m (6562 ft)
265V (continuous),
Reinforced Insulation Type
75V (continuous),
Reinforced Insulation Type
Routine tested at
2596V DC for 1s, AC Power
Routine tested at
Input to System and AC
1697V DC for 1s, DC Power
Power Input to 24V DC
Input to System
User Power
100VA @ 120V AC
50VA @ 24V DC
130VA @ 240V AC
8 W @ 60 °C (140 °F)
7.5 W @ 60 °C (140 °F)
2.0 A
2.0 A
0.8 A
0.8 A
25 A @ 132V AC
30 A @ 31.2V DC
Littelfuse 02153.15MXP
Littelfuse 021706.3MXP
118 x 70 x 87 mm (4.65 x 2.76 x 3.43 in.)
height including mounting tabs is 138 mm (5.43 in.)
485 g (1.07 lb)
1 on power ports
2 on power ports
2
2.5 mm
(14 AWG) solid copper wire rated at 90 °C (194 °F), or greater, 1.2 mm (3/64 in.) insulation max
T3C
N/A
T4
None (open-style)
Rockwell Automation Publication 1769-IN028I-EN-P - July 2020
Compact I/O Expansion Power Supplies
1769-PA4, 1769-PA4K
1769-PB4, 1769-PB4K
85...265V AC
19.2...32V DC
47...63 Hz
N/A
265V (continuous),
75V (continuous),
Reinforced Insulation Type
Reinforced Insulation Type
(IEC Class 1 grounding
(IEC Class 1 grounding
required)
required)
Routine tested at
Routine tested at
2596V DC for 1s, AC Power
1697V DC for 1s, DC Power
Input to System
Input to System
200VA @ 120V AC
100VA @ 24V DC
240VA @ 240V AC
18 W @ 60 °C (140 °F)
14.5 W @ 60 °C (140 °F)
4.0 A
4.0 A
2.0 A
2.0 A
25 A @ 132V AC
30 A @ 31.2V DC
Littelfuse 02183.15MXP
Littelfuse 0217008.MXP
500 g (1.10 lb)
1 on power ports
2 on power ports
N/A
T4
29

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents