Ametek TR-2100 Operation Manual page 76

Multi - function recorder
Table of Contents

Advertisement

TR-2100 User Manual
Status Relays
Type
Number of outputs
Contact rating
Indication
Isolation
Power Supply
Input voltage options
Power requirement
Backup batteries
Cooling
Voltage Withstand
Isolation
Impulse voltage withstand
Surge withstand
RFI
ESD
Enclosure
Cabinet
Solid State
4
1 Amp max
400 V dc / 280 Vac max
Power & on line are N/C
Attention & triggered are N/O
Power OK
System on line
Attention
System Triggered
Input to output - 2500 V ac
Contact to contact - 600 V dc
88 - 370 V dc, 85 - 264 V ac
24 / 48 V dc optional
120 VA Max.
Internal batteries for real-time clock and parameter
memory
Long life fans on rear panel & processor
2.5 kV RMS for 1 minute, Channel to channel, channel
to ground. (per IEC 255-5)
2.15 kV dc for PSU (Power Supply Unit)
5 kV, 1.2/50 µs. 0.5 Joule
(per IEC 255-5)
2.5 kV, 1 MHz damped sine wave
(per IEC 255-22-1; IEEE/ANSI C37.90.1-1989)
(per IEC 801 -3 & IEC 801-6 & IEEE/ANSI C37.90.2)
(per IEC 801-2)
Steel 19" rack mounting cabinet
70

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents