AGL402 (3.0 ... 11.0 kW, 400 V)
Type
Agile
402
Size
Output motor side
Recommended motor shaft
power
Output current
Long-term overload
current (60 s)
Short-time overload
current (1 s)
Switching frequency
Output, brake resistor
Minimum brake resistor
Recommended brake resistor
(770 V)
Input mains side
Rated current
Maximum mains current
Fuses
Fuses UL type
Mechanics
2)
Dimensions
Weight (approx.)
Degree of protection
Terminals
Installation
Interior fan
Heat sink fan

Ambient conditions

Power dissipation (2 kHz switch-
ing frequency)
1) According to DIN EN 61800-5-1.
2) Dimensions of the basic device.
05/2013
P
kW
I
A
I
A
I
A
f
kHz
R
R
I
A
1)
I
A
I
A
I
A
HxWxD mm
m
kg
-
-
2
A
mm
-
-
-
-
-
-
P
W
49
T
+31(0)88 7865800
400 V, 3-phase
-15
-18
-19
2
3.0
4.0
5.5
7.5
9.5
12.0
13.0
11.2
14.2
18.0
19.5
15.0
19.0
24.0
26.0
2, 4, 8, 16
106
106
106
148
106
106
6.8
7.8
13.8
14.2
9.8
12.8
17.2
17.2
10
10
16
Bussmann
FWP-20A14Fa
200 x 80 x 196
1.5
IP20 (EN60529)
Mains and motor
terminals:
Terminals relay output: 0.1 ... 1.5
vertical
133
167
230
235
Quick Start Guide
I
elsto.eu
-19
-21
-22
-23
3
5.5
7.5
9.2
11.0
17.0
20.0
23.0
25.5
30.0
34.5
34.0
40.0
43.0
48
48
48
48
80
58
48
48
15.8
20.0
26.0
23.0
28.1
33.6
16
25
25
35
Bussmann
FWP-30A14Fa
200 x 125 x 205
3
0.2 ... 4 (flexible with
sleeve)
0.2 ... 6 (rigid)
yes
yes
321
393