Defrosting; Safety Circuit; Compressor Control; Maintenance - Dantherm CDF 10 Manual

Hide thumbs Also See for CDF 10:
Table of Contents

Advertisement

NOTE! If the air humidity is below 50%RH, the unit will not
start when the power is connected.

4.3 Defrosting

If the temperature falls to below 20ºC the evaporator may start to ice up after a short time.
The defrosting function is activated when the evaporator sensor registers a temperature lower than 5ºC, after which
the control will let the unit operate in dehumidification mode for another 30 minutes. Then the compressor is
stopped and the unit switches over to active defrosting, which means that the cooling circuit turns and the hot
refrigerant runs through the evaporator coil and melts the ice. When the evaporator sensor registers that the
temperature is above 5ºC, the compressor starts again.

4.4 Safety circuit

If the temperature in the dehumidifier increases to a temperature of more than 55ºC (for example in case of fan
failure), the compressor stops automatically to avoid damaging it. After 45 minutes the compressor starts again
automatically.
By room temperatures outside the unit's working range (3 - 32°C) it is automatically switched off to protect the
evaporator coil from icing up and the condenser coil from overheating. The unit will automatically start again when
the room temperature is within the working range.

4.5 Compressor control

The number of compressor starting is limited by a 6 minutes timer, which starts up when switching on the
compressor. The timer must have come to an end before the compressor can be switched on again.
Each time the unit has been switched off on the main switch, by the built-in hygrostat, or by an external hygrostat,
it will take 30 seconds before the unit can be switched on again. This is a safety function protecting the compressor
against overloading caused by too high pressure in the cooling circuit at start up.

5. Maintenance

The dehumidifier requires very little attention for trouble free running. All the necessary safety and control
functions have been built in. The fan motor and the compressor have permanent lubrication and require no
particular maintenance.

5.1 Cleaning of filter

Once a month the air inlet filter should be checked and cleaned if necessary. The front cover panel is removed and
the filter taken out. Clean the filter in tepid soapy water or if not badly soiled by vacuum cleaning.