5.2 Cleaning of the dehumidifier

Once a year the front cover panel should be removed in order to check the inside of the dehumidifier. If the
dehumidifier is dirty it should be cleaned by vacuum cleaning. The condenser in particular should be thoroughly
vacuumed. If the lamella evaporator is badly soiled, it may be washed in tepid soapy water.

6. Faults and how to remedy them

The dehumidifier does not start when power is connected
1. Check external fuses
2. Check that the power supply to the units is correct
3. Check that the switch on the side is ON
4. Check the built-in hygrostat by setting it on a lower relative humidity. This is done by turning the hygrostat
knob clockwise. If the unit does not start, check the built-in hygrostat for faults.
The unit was switched off automatically. If it starts after 45 minutes, but switches off again shortly
afterwards, check the following:
5. Check that the fan is running when the unit starts after 45 minutes
6. Check whether the condensor coil is dirty
7. Check whether the filter is dirty
8. Check whether the room temperature is above 32ºC. If so, and the unit has not automatically been switched
off, it should be switched off.
9. Check that the air inlet on the front and the air outlet through the grill on the sides are not blocked.
The evaporator coil has iced up and the unit does not separate water
10. Check whether the room temperature is below 3°C. If so, and the unit has not automatically been switched
off, it should be switched off.
If you cannot find the reason for the fault, switch off the unit immediately in order to prevent further damage.
Contact a service technician or a Dantherm representative.
NOTE! If the dehumidifier is not functioning
Disposal
This unit contains refrigerant type R134a and compressor oil. When scrapping the unit, bring the compressor to a
place of discharge, which is approved by the authorities.
correctly, shut it down immediately.