3.0 Product Certifications

Rev 1.2
3.1 European Directive Information
A copy of the EU Declaration of Conformity can be found at the end of the Quick
Start Guide. The most recent revision of the EU Declaration of Conformity can be
found at EmersonProcess.com/Rosemount.
3.2 Ordinary Location Certification
As standard, the transmitter has been examined and tested to determine that the
design meets the basic electrical, mechanical, and fire protection requirements
by a nationally recognized test laboratory (NRTL) as accredited by the Federal
Occupational Safety and Health Administration (OSHA).
3.3 North America
E5 USA Explosionproof (XP) and Dust-Ignitionproof (DIP)
Certificate: 0T2H0.AE
Standards: FM Class 3600 – 2011, FM Class 3615 – 2006, FM Class 3810 – 2005,
Markings: XP CL I, DIV 1, GP B, C, D; DIP CL II, DIV 1, GP E, F, G; CL III;
I5 USA Intrinsic Safety (IS) and Nonincendive (NI)
Certificate: 1Q4A4.AX
Standards: FM Class 3600 – 2011, FM Class 3610 – 2010, FM Class 3611 – 2004,
Markings: IS CL I, DIV 1, GP A, B, C, D; CL II, DIV 1, GP E, F, G; Class III; DIV 1 when
Special Conditions for Safe Use (X):
1. The Rosemount 3051 Transmitter housing contains aluminum and is considered a
potential risk of ignition by impact or friction. Care must be taken into account during
installation and use to prevent impact and friction.
2. The Rosemount 3051 Transmitter with the transient terminal block (Option code T1)
will not pass the 500 Vrms dielectric strength test and this must be taken into account
during installation.
IE USA FISCO
Certificate: 1Q4A4.AX
Standards: FM Class 3600 – 2011, FM Class 3610 – 2010, FM Class 3611 – 2004,
Markings: IS CL I, DIV 1, GP A, B, C, D when connected per Rosemount drawing
Special Conditions for Safe Use (X):
1. The Rosemount 3051 Transmitter housing contains aluminum and is considered a
potential risk of ignition by impact or friction. Care must be taken into account during
installation and use to prevent impact and friction.
2. The Rosemount 3051 Transmitter with the transient terminal block (Option code T1)
will not pass the 500 Vrms dielectric strength test and this must be taken into account
during installation.
20
ANSI/NEMA 250 – 2003
T5(–50 °C ≤ T
≤ +85 °C); Factory Sealed; Type 4X
a
FM Class 3810 – 2005
connected per Rosemount drawing 03031-1019; NI CL 1, DIV 2, GP A, B, C,
D; T4(–50 °C ≤ T
≤ +70 °C) [HART
a
T4(–50 °C ≤ T
≤ +60 °C) [Fieldbus/PROFIBUS
a
FM Class 3810 – 2005
03031-1019 (–50 °C ≤ T
], T5(–50 °C ≤ T
®
≤ +60 °C); Type 4x
a
August 2016
≤ +40 °C) [HART];
a
®
]; Type 4x