3. Intrinsically Safe parameters:
Parameter
Voltage U
Current I
i
Power P
i
Capacitance C
Inductance L
Note 1: FISCO parameters apply to both Group IIC and IIB.
Note 2: [For Flowmeters] When Rosemount 644 Temperature Transmitter is used, the
transmitter should be used with Ex-certified associated apparatus to establish explosion
protection system that can be used in explosive gas atmospheres. Wiring and terminals
should comply with the instruction manual of both Rosemount 644 and associated
apparatus. The cables between Rosemount 644 and associated apparatus should be
shielded cables (the cables must have insulated shield). The shielded cable has to be
grounded reliably in a non-hazardous area.
4. Transmitters comply with the requirements for FISCO field devices specified in
IEC60079-27:2008. For the connection of an intrinsically safe circuit in accordance with
FISCO Model, FISCO parameters are listed in the table above.
5. The product should be used with Ex-certified associated apparatus to establish
explosion protection system that can be used in explosive gas atmospheres. Wiring and
terminals should comply with the instruction manual of the product and associated
apparatus.
6. The cables between this product and associated apparatus should be shielded cables
(the cables must have insulated shield). The shielded cable has to be grounded reliably
in a non-hazardous area.
7. End users are not permitted to change any intern components but to settle the problem
in conjunction with the manufacturer to avoid damage to the product.
8. During installation, use and maintenance of this product, observe the following
standards: GB3836.13-1997, GB3836.15-2000, GB3836.16-2006, GB50257-1996,
GB12476.2-2006, GB15577-2007.
N3 China Type n
Certificate: GYJ15.1105X
Standards: GB3836.1-2010, GB3836.8-2003
Markings: Ex nA nL IIC T5 Gc (–40 °C ≤ T
Special Condition for Safe Use (X):
1. Symbol "X" is used to denote specific conditions of use: The apparatus is not capable of
withstanding the 500 V test to earth for one minute. The must be taken into
consideration during installation.
3.8 Japan
E4 Japan Flameproof
Certificate: TC20577, TC20578, TC20583, TC20584 [HART]; TC20579, TC20580,
Markings: Ex d IIC T5
i
200 mA
0.012 μF
i
i
TC20581, TC20582 [Fieldbus]
HART
Fieldbus/PROFIBUS
30 V
300 mA
0.9 W
1.3 W
0 mH
≤ +70 °C)
a
Quick Start Guide
FISCO
30V
17.5 V
380 mA
5.32 W
0 μF
<5 nF
<10 μH
0mH