August 2016
Note
Guided setup will automatically go through each step in the proper order.
Enter the desired damping value in seconds. The permitted range of
values is 0.4 to 60 seconds.
b. To use manual setup:
Navigate to Configure>Manual Setup>Process Variable.
Select Change Damping.
Enter the desired damping value in seconds. The permitted range of
values is 0.4 to 60 seconds.
8. Configure optional LCD display (if installed).
a. To use guided setup:
Navigate to Configure>Guided Setup.
Select Local Display Setup.
Note
Guided setup will automatically go through each step in the proper order.
Check the box next to each parameter to be displayed to a maximum of
four parameters. The LCD display will continuously scroll through the
selected parameters.
b. To use manual setup:
Navigate to Configure>Guided Setup.
Select Local Display Setup.
Check each parameter to be displayed. The LCD display will
continuously scroll through the selected parameters.
9. Review transmitter configuration and place in service.
a. To review the transmitter configuration, navigate using the manual setup
navigation sequences for "AI Block Unit Setup", "Change Damping", and
"Set up LCD Display".
b. Change any values as necessary.
c. Return to the Overview screen.
d. If mode is "Not in Service", select the Change button, and then select
Return All to Service.
Note
If hardware or software write protection is not needed,
10. Set switches and software write lock.
a. Check switches (see
Note
The write lock switch can be left in the locked or unlocked position. The simulate
enable/disable switch may be in either position for normal device operation.
Figure
7).
Quick Start Guide
Step 10
can be skipped.
17