ClimateMaster trilogy 45 q-mode series User Manual

ClimateMaster trilogy 45 q-mode series User Manual

Variable speed horizontal vertical and downflow earthpure systems sizes 0930–1860

Advertisement

Trilogy
45
®
Q-Mode
(QE) Series
®
VARIABLE SPEED
HORIZONTAL VERTICAL AND DOWNFLOW
EARTHPURE
SYSTEMS SIZES 0930–1860
®

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the trilogy 45 q-mode series and is the answer not in the manual?

Questions and answers

Summary of Contents for ClimateMaster trilogy 45 q-mode series

  • Page 1 Trilogy ® Q-Mode (QE) Series ® VARIABLE SPEED HORIZONTAL VERTICAL AND DOWNFLOW EARTHPURE SYSTEMS SIZES 0930–1860 ®...
  • Page 2 Trilogy ® 45 Q-Mode ® (QE) Series ClimateMaster: Declare your personal energy independence.
  • Page 3: Table Of Contents

    Trilogy ® 45 Q-Mode ® (QE) Series Table of Contents What’s New With The Trilogy 45 (QE)? ......4-5 ® Physical Data ..................38 iGate Web-Enabled Communicating Controls ....6 ® Dimensions — Vertical Upfl ow ........39-40 Q-Mode ....................7 ® Service Access — Vertical Upfl ow ...........41 iGate ClimaZone ................
  • Page 4: What's New With The Trilogy ® 45 (Qe)

    ® delivers unsurpassed effi ciency and will set ClimateMaster dealers in a class of their own in comfort and humidity control by precisely matching capacity to the the home heating and cooling market. It is the fi rst geothermal heat heating and cooling load while also operating at very low sound pump ever certifi...
  • Page 5 Trilogy ® unit, ClimateMaster offers a PC/laptop tool to confi gure control for ground loop geothermal applications, which includes: and diagnose the system. PC/laptop loaded with the software plugs three-way fl ush valves and ports, expansion tank, high effi ciency...
  • Page 6: Igate ® Web-Enabled Communicating Controls

    ® ® Trilogy iGate System ClimateMaster: Declare your personal energy independence.
  • Page 7: Q-Mode

    Trilogy ® 45 Q-Mode ® (QE) Series Q-Mode ® ® ® The industry’s fi rst and patent pending Q-Mode delivers four While Trilogy ’s 45 EER and 5.1 COP are impressive, what modes of operation to deliver the highest effi ciencies across sets it in a league of its own is the ADDITIONAL savings all AHRI rating points.
  • Page 8: Igate ® Climazone Tm

    Zone Damper – up to 3 per zone • Transformer – for damper and thermostat power • Trilogy PC Service Tool Outdoor Temperature Sensor • Indoor Remote Temperature Sensor • Wall Mounted Remote Indoor Temperature sensor ClimateMaster: Declare your personal energy independence.
  • Page 9: Igate ® Connect

    Trilogy ® 45 Q-Mode ® (QE) Series iGate Connect ® ® ® iGate Connect features a variety of ways to access and control your Trilogy Geothermal Heating and Cooling System. ONNECT Web-Enabled Home Thermostat Web Portal Accessible Any Time, Any Where •...
  • Page 10: Trilogy ® Pc Service Tool

    Serial # updates Hot water delta T Aux. heat operating mode Thresholds (limits) Cooling + Hot-Water % Cooling + Hot-Water offset Heating + Hot-water cutout Heating + Hot-water cutout offset Cooling-Dehumid cutout Anticipator Compressor ASCD minutes ClimateMaster: Declare your personal energy independence.
  • Page 11 Trilogy ® 45 Q-Mode ® (QE) Series Trilogy PC Service Tool – Exclusively Available on Trilogy Q-Mode ® ® ® Service mode/ clear fault history Enter service mode Manual operation: Operating mode Target airfl ow Loop pump speed Hot water pump speed Clear Fault History Diagnostics / REAL-TIME operating data: The service tool software includes fi...
  • Page 12: Internet Dealer Portal

    (QE) Series Internet Dealer Portal ® ClimateMaster has taken the convenience of monitoring, confi guring and diagnosing the Trilogy to the next level by making all unit operating information available on the internet through the dealer portal. The dealer portal is your gateway to all your iGate ®...
  • Page 13 (see section below) to fi nd possible causes and instructions on fi xing the issue. Smart phone App The Climatemaster Trilogy ® Troubleshooter allows GeoElite service technicians access to the latest, web-based information* on any of the 90+ pos-...
  • Page 14: Igate Smart Tank

    Inlet port for incoming water from the heat pump. Bowl-shaped bottom for more complete sediment draining. Side cut-away view of the iGate ® Full port ball vale for fast Smart Tank water drainage. ClimateMaster: Declare your personal energy independence.
  • Page 15: Vflow ® Internal Variable Water Flow Control

    Trilogy ® 45 Q-Mode ® (QE) Series vFlow Internal Variable Water Flow Control ® ® vFlow Internal Variable Water Flow Energy Savings with water circulation control Industry-fi rst, built-in vFlow replaces a traditionally ineffi cient, Units with vFlow deliver higher operating cost savings by ®...
  • Page 16: Design Features

    Far simpler than the • UPS (Unit Performance Sentinel) provides early warning of use of dip switches on the unit control board. ineffi cient operation. ClimateMaster: Declare your personal energy independence.
  • Page 17 ® communicating control provides advanced unit functionality • ClimateMaster goes even further to back up its commitment to and comprehensive confi guration, monitoring and diagnostic quality by including a service labor allowance for the fi rst fi ve capabilities through digital communication links with the variable-...
  • Page 18: Unit Model Key

    REVISION LEVEL A = Current Revision CABINET 0 = Residential VOLTAGE G = 208-230/60/1 CONTROLS E = EXM NOTE: Above model nomenclature is a general reference. Consult individual specifi cation sections for detailed information. ClimateMaster: Declare your personal energy independence.
  • Page 19: Ahri/Iso/Ashrae 13256-1

    Trilogy ® 45 Q-Mode ® (QE) Series AHRI/ISO/ASHRAE 13256-1 ASHRAE/AHRI/ISO 13256-1 Water Loop Heat Pump Ground Water Heat Pump Ground Loop Heat Pump Cooling Heating Capacity Cooling 86°F Heating 68°F Cooling 59°F Heating 50°F Full Load 77°F Full Load 32°F Model Modulation Part Load 68°F...
  • Page 20: Reference Calculations & Legend

    = Water coil pressure drop (ft hd) = hot water capacity, Mbtuh = Energy Effi ciency Ratio = BTU output/Watt input UPFLOW HORIZONTAL Straight Discharge Left Return Air Right Return Air Piping End Straight Discharge ClimateMaster: Declare your personal energy independence.
  • Page 21: Entering Air Correction Factors

    Trilogy ® 45 Q-Mode ® (QE) Series Entering Air Correction Factors Cooling Sensible Cooling Capacity Multiplier - Entering Total Heat of Entering DB °F Power Capacity Rejection WB°F 80.6 0.734 1.046 1.017 0.770 0.853 0.811 0.871 1.062 1.240 1.017 0.837 0.896 0.890 0.666...
  • Page 22: Trilogy 45 Q-Mode (Qe) Series

    Above performance is based on 70°F db entering air condition. Interpolation is permissable, extrapolation is not. Above data is based on 15% methanol. Table does not include fan or pump power corerctions for AHRI/ISO conditions. ClimateMaster: Declare your personal energy independence.
  • Page 23 Trilogy ® 45 Q-Mode ® (QE) Series Performance Data — Trilogy QE 0930 Heating ® LWT(°F) WPD(ft. of hd) 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0...
  • Page 24 Interpolation is permissable, extrapolation is not. Above data is based on 15% methanol. Performance data in shaded area will be reduced for operating voltages below 240 vac. Table does not include fan or pump power corerctions for AHRI/ISO conditions. ClimateMaster: Declare your personal energy independence.
  • Page 25 Trilogy ® 45 Q-Mode ® (QE) Series Performance Data — Trilogy QE 0930 Cooling ® LWT(°F) WPD(ft. of hd) 53.4 51.5 45.2 37.8 30.9 65.0 65.0 65.0 65.0 65.0 0.4 0.6 0.9 1.2 1.5 64.7 62.3 50.8 39.8 31.3 65.0 65.0 65.0 65.0...
  • Page 26 83.0 13.3 0.85 10.4 143.0 13.2 0.87 10.2 145.0 13.1 0.90 10.0 147.0 * pressure drop is less than 1 ft Interpolation is permissable, extrapolation is not. Above data is based on 15% methanol. ClimateMaster: Declare your personal energy independence.
  • Page 27 Trilogy ® 45 Q-Mode ® (QE) Series Performance Data — Trilogy QE 0930 Hot Water ® High EWTS LWTS °F EWTL COP Hz LWTL 14.0 26.1 2.02 19.2 78.0 14.0 24.4 2.41 16.2 98.0 14.0 20.7 2.52 12.1 118.0 14.0 13.3 1.83 138.0...
  • Page 28 9.0 12.0 18.0 18.0 18.0 7.6 10.3 15.3 15.3 15.3 0.85 0.86 0.85 0.85 0.85 12.9 17.0 26.0 26.0 26.0 * pressure drop is less than 1 ft Above performance is based on 80°F db / 67°F wb entering air conditions. ClimateMaster: Declare your personal energy independence.
  • Page 29 Trilogy ® 45 Q-Mode ® (QE) Series Performance Data — Trilogy QE 0930 Cooling and Hot Water ® HW LWT HW GPM HW PD 27.6 27.5 25.5 22.8 19.9 82.0 82.0 82.0 82.0 82.0 1.7 2.2 3.4 4.6 5.9 1.4 2.6 3.9 31.5 31.1 28.6...
  • Page 30 Interpolation is permissable, extrapolation is not. Above data is based on 15% methanol. Performance data in shaded area will be reduced for operating voltages below 240 vac. Table does not include fan or pump power corerctions for AHRI/ISO conditions. ClimateMaster: Declare your personal energy independence.
  • Page 31 Trilogy ® 45 Q-Mode ® (QE) Series Performance Data — Trilogy QE 1860 Heating ® LWT(°F) WPD(ft. of hd) 14.0 14.0 14.0 14.0 14.0 11.2 14.0 14.0 14.0 14.0 14.0 10.1 12.2 14.0 14.0 14.0 14.0 14.0 10.3 12.3 18.0 18.0 18.0 18.0...
  • Page 32 Interpolation is permissable, extrapolation is not. Above data is based on 15% methanol. Performance data in shaded area will be reduced for operating voltages below 240 vac. Table does not include fan or pump power corerctions for AHRI/ISO conditions. ClimateMaster: Declare your personal energy independence.
  • Page 33 Trilogy ® 45 Q-Mode ® (QE) Series Performance Data — Trilogy QE 1860 Cooling ® LWT(°F) WPD(ft. of hd) 68.1 59.4 44.2 34.7 28.6 65.0 65.0 65.0 65.0 65.0 0.8 1.1 1.7 2.3 3.0 86.6 67.8 46.9 35.8 27.6 65.0 65.0 65.0 65.0...
  • Page 34 83.0 24.9 1.74 18.9 143.0 24.4 1.78 18.3 145.0 24.0 1.83 17.7 147.0 * pressure drop is less than 1 ft Interpolation is permissable, extrapolation is not. Above data is based on 15% methanol. ClimateMaster: Declare your personal energy independence.
  • Page 35 Trilogy ® 45 Q-Mode ® (QE) Series Performance Data — Trilogy QE 1860 Hot Water ® High EWTS LWTS °F EWTL COP Hz LWTL 14.0 47.2 4.31 32.5 82.0 14.0 45.1 5.42 26.6 102.0 14.0 39.1 5.81 19.3 122.0 14.0 27.2 5.23 142.0...
  • Page 36 18.0 24.0 28.0 28.0 28.0 12.4 16.7 19.6 19.6 19.6 0.69 0.70 0.70 0.70 0.70 2.20 3.12 3.97 3.97 3.97 25.5 34.7 41.5 41.5 41.5 * pressure drop is less than 1 ft Above performance is based on 80°F db / 67°F wb entering air conditions. Interpolation is permissable, extrapolation is not. ClimateMaster: Declare your personal energy independence.
  • Page 37 Trilogy ® 45 Q-Mode ® (QE) Series Performance Data — Trilogy QE 1860 Cooling and Hot Water ® HW LWT HW GPM HW WPD 28.9 33.9 27.0 20.0 15.8 82.0 82.0 82.0 84.0 88.2 3.4 4.4 6.8 8.0 8.0 1.1 1.8 4.1 5.8 5.8 32.8 33.6 29.2...
  • Page 38: Physical Data

    2 - 18 x 18 [457 x 508] MERV11 Throwaway, in [mm] [457 x 457] 1 - 20 x 24 [508 x 610] Weight - Operating, lbs [kg] 298 [135] 448 [203] Weight - Packaged, lbs [kg] ClimateMaster: Declare your personal energy independence.
  • Page 39: Dimensions - Vertical Upfl Ow

    Trilogy ® 45 Q-Mode ® (QE) Series Dimensions - Vertical Upfl ow Trilogy ® Legend CAP= Control Access Panel CSP=Compressor Service Panel BSP=Blower Service Panel PSP=Pump and Flow Meter Service Panel Field Installed Discharge Flange Deluxe Filter Bracket Drai Air Coil Air Coil Side Air Coil Side Frame Depth...
  • Page 40 Unit shipped with deluxe duct collar/fi lter frame extending from unit 3” [7.6cm] and is suitable for duct connection. Discharge fl ange is fi eld installed. [41.3 mm] [40.5 mm] [40.5 mm] [40.5 mm] [50.0 mm] [34.9 mm] [44.5 mm] Front-View Front-View QE0930 QE1860 ClimateMaster: Declare your personal energy independence.
  • Page 41: Service Access - Vertical Upfl Ow

    Trilogy ® 45 Q-Mode ® (QE) Series Service Access - Vertical Upfl ow Trilogy ® Left Return Supply Air Opening Front CAP and BSP Right Return Supply Air Opening Front CAP and BSP = mandatory 2 service access = (optional) additional 2 service access Notes: 1.
  • Page 42: Dimensions - Vertical Downfl Ow

    Return Width Depth Return Depth Height 10.8 22.2 26.2 21.9 0930 17.1 21.4 25.3 23.0 27.4 56.4 66.5 55.6 13.1 12.9 10.4 27.2 30.2 23.9 1860 18.7 22.9 33.3 32.7 26.5 69.1 76.7 60.7 ClimateMaster: Declare your personal energy independence.
  • Page 43 Trilogy ® 45 Q-Mode ® (QE) Series Dimensions - Vertical Downfl ow Trilogy ® Water Connections Vertical Loop Downfl ow Cond. Water Model Drain Condensate 18.36 13.87 4.62 5.54 2.62 1” 1” 3/4" 0930 46.6 35.2 11.7 14.1 Swivel Swivel 18.36 13.87 4.62...
  • Page 44: Service Access - Vertical Downfl Ow

    PSP = Pump and Flow Meter Service Panel compressor, pump volute, or heat exchanger replacement is required. 3. Top supply air is shown, the same clearances apply to bottom supply air units. ClimateMaster: Declare your personal energy independence.
  • Page 45: Dimensions - Horizontal

    Trilogy ® 45 Q-Mode ® (QE) Series Dimensions - Horizontal Trilogy ® Legend CAP= Control Access Panel CSP=Compressor Service Panel BSP=Blower Service Panel PSP=Pump and Flow Meter Service Panel FAP=Filter Drier Access Panel Unit Hanger Detail Model Blower 62.1 157.7 24.5 62.2 20.25...
  • Page 46 13.8 18.2 Condensate is 3/4” MPT. Unit shipped with deluxe duct collar/fi lter rack extending from unit 3” [7.6cm] and is suitable for duct connection. Discharge fl ange and hanger brackets are factory installed. ClimateMaster: Declare your personal energy independence.
  • Page 47: Service Access - Horizontal

    Trilogy ® 45 Q-Mode ® (QE) Series Service Access - Horizontal Trilogy ® Left Return Back Discharge Right Return Back Discharge Supply Supply Air Flow Air Flow Return Return Air Flow Air Flow Front Front Left Return Straight Discharge Right Return Straight Discharge Supply Supply Return...
  • Page 48: Electrical Data

    (QE) Series with Internal Flow Controller Compressor Total Max/ Volt Rated Voltage Model Pump Loop Motor Unit Circuit Fuse Code Voltage Min/Max Amps HACR 0930 208/230/60/1 197/254 20.0 20.0 24.8 29.8 1860 208/230/60/1 197/254 28.0 28.0 37.1 44.1 ClimateMaster: Declare your personal energy independence.
  • Page 49: Standard Electrical Wiring Diagram

    Trilogy ® 45 Q-Mode ® (QE) Series Trilogy 45 Internal Flow Controller Electrical Wiring Diagram - ® 96B0005N64 Residential Products Technical Guide...
  • Page 50: Ecm Blower Performance Data

    Maximum 2250 2250 42,000 1600 1600 1600 48,000 1825 1825 1825 54,000 2025 2025 2025 60,000 2250 2250 2250 Airfl ow is controlled within 5% up to the Max ESP shown with wet coil ClimateMaster: Declare your personal energy independence.
  • Page 51: Pump Curves Data

    Trilogy ® 45 Q-Mode ® (QE) Series Pump Curves Data Magna Geo 25-140 (High Head) Pump Curve Table GPM Head (ft) Magna Geo 25-140 Pump Curve 44.7 45.4 46.1 46.8 47.5 47.7 47.1 46.1 45.3 43.9 10.0 42.6 11.0 41.2 12.0 39.9 13.0...
  • Page 52: Auxiliary Heat Ratings

    40.0 34.7 50.0 43.4 Dual - L3/L4 40.0 34.7 50.0 43.4 All heaters rated single phase 208/240V 60Hz All Fuses UL Class K general purpose All models 12kW or larger feature internal circuit breakers ClimateMaster: Declare your personal energy independence.
  • Page 53: Accessories, Options, And Warranty

    Normally, the dealer or service organization who installed the products will provide warranty performance for the owner. Should the installer be unavailable, contact any CM recognized distributor, dealer or service organization. If assistance is required in obtaining warranty performance, write or call: Climate Master, Inc. • Customer Service • 7300 SW 44th Street • Oklahoma City, Oklahoma 73179 • (405) 745-6000 • e-service@climatemaster.com horizontal units).
  • Page 54 Trilogy ® 45 Q-Mode ® (QE) Series Notes ClimateMaster: Declare your personal energy independence.
  • Page 55 Trilogy ® 45 Q-Mode ® (QE) Series Residential Products Technical Guide...
  • Page 56: Revision History

    RP945 ClimateMaster works continually to improve its products. As a result, the design and specifi cations of each product at the time for order may be changed without notice and may not be as described herein. Please contact ClimateMaster’s Customer Service Department at 1-405-745-6000 for specifi...