Tranquility 27™ (TT) Series Tranquility 20™ (TS) Series Tranquility 16™ (TC) Series Genesis Ultra (GS) Series Table of Contents Model Nomenclature Genesis Standard (GR) Series Storage Genesis Compact (GC) Series Pre-Installation Physical Data 6-11 Horizontal Unit Installation Field Conversion of Air Discharge Condensate Piping Installation Duct System Installation Vertical Unit Location...
C L I M AT E M A S T E R W AT E R - S O U R C E H E AT P U M P S P a c k a g e d U n i t s R e v.
Page 13
UV based anti-bacterial systems Therefore, fi lter rails are the industry standard and are included on ClimateMaster commercial heat pumps for the purposes of may damage e-coated air coils. holding the fi lter only. For ducted return applications, the fi lter rail must be removed and replaced with a duct fl...
fi nger-tight plus one quarter turn. Tighten steel fi ttings unnecessary noise complaints. as necessary. Figure 11: Supply/Return Hose Kit Optional pressure-rated hose assemblies designed specifi cally for use with ClimateMaster units are available. Swivel Brass Brass Similar hoses can be obtained from alternate suppliers.
3.5 gpm per ton [2.9 and 4.5 l/m per kW] of cooling (except GC series) include low temperature-soldered capacity. ClimateMaster recommends 3 gpm per ton bracket-supported IPT water connections, which do not [3.9 l/m per kW] for most applications of water loop heat require a backup wrench.
17. Optional ECM motor (TT/TS units only) speeds are set via low voltage controls (see “ECM Blower Control”). Most ClimateMaster units are shipped on the medium speed tap. Consult submittal data or engineering design guide for specifi c unit airfl ow tables. Typical unit design delivers rated airfl...
10°F [-12.2°C] refrigerant temperature, a more suitable temperature when using an antifreeze solution. Fan Motor All ClimateMaster units operating with entering water temperatures below 59°F [15°C] must include the ELECTRICAL - LOW VOLTAGE WIRING optional water/refrigerant circuit insulation package to prevent internal condensation.
24VAC external solenoid valve. Figures 22 and 23 illustrate typical slow closing water control valve wiring for Taco 500 series (ClimateMaster P/N AMV…) JW3 should never be clipped for GC series and Taco ESP series valves. Slow closing valves take...
Page 47
300 psig and a cut-in pressure of 250 psig. This pressure switch can be ordered from ClimateMaster with a 1/4” internal fl are connection as part number 39B0005N02. c l i m a t e m a s t e r. c o m...
DXM or ECM control board. Practically any heat pump the thermostat back plate against the wall so that it thermostat will work with ClimateMaster units, provided it appears level and so the thermostat wires protrude has the correct number of heating and cooling stages.
Table 6b: DXM LED And Alarm Relay Operations (refrigerant temperature). Note: This jumper should only be clipped under extenuating circumstances, Status LED Test LED Description of as recommended by ClimateMaster technical Fault LED (red) Alarm Relay Operation (green) (yellow) services.
Page 69
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y P a c k a g e d U n i t s R e v.
The cooling/heating modes are like any other Heating. When the call is satisfi ed at the thermostat ClimateMaster WSHP. The reversing valve (“O” signal) the unit will continue to run in 1st Stage Heating is energized in cooling, along with the compressor until the call is removed or satisfi...
Page 73
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y P a c k a g e d U n i t s R e v.
ClimaDry to operate properly. refi lled and bled, check the main system panels, 4. Verify that all strainers are in place (ClimateMaster safety cutouts and alarms. Set the controls to properly recommends a strainer with a #20 stainless steel wire maintain loop temperatures.
5. Two factors determine the operating limits of temperature until the compressor activates. ClimateMaster heat pumps, (a) return air temperature, c. Check for warm air delivery within a few minutes and (b) water temperature. When any one of these factors after the unit has begun to operate.
97B0045N02 ClimateMaster works continually to improve its products. As a result, the design and specifi cations of each product at the time for order may be changed without notice and may not be as described herein. Please contact ClimateMaster’s Customer Service Department at 1-405-745-6000 for specifi...