Model Nomenclature: General Overview 4 5 6 0 2 6 0 2 C L T STANDARD SERIES S = Standard TE = Tranquility 30 Digital SUPPLY AIR FLOW & MOTOR CONFIGURATION CONFIGURATION Supply Configuration V = Vertical Up H = Horizontal...
® Tranquility 30 Digital (TE) Series IOM - 60Hz HFC-410A PRE LI MI NA RY R e v. : 3 A u g . , 2 0 1 2 B General Information Inspection CAUTION! Upon receipt of the equipment, carefully check the shipment against the bill of lading.
® Tranquility 30 Digital (TE) Series IOM - 60Hz HFC-410A PR EL I MI N ARY R e v. : 3 A u g . , 2 0 1 2 B Vertical Installation Figure 2: Service Access Vertical Unit Location Packaged units are not designed for outdoor installation.
® Tranquility 30 Digital (TE) Series IOM - 60Hz HFC-410A PRE LI MI NA RY R e v. : 3 A u g . , 2 0 1 2 B Horizontal Installation Horizontal Unit Location Mounting Horizontal Units Packaged units are not designed for outdoor installation. Horizontal units have hanger kits pre-installed from the Locate the unit in an INDOOR area that allows enough space factory as shown in Figure 4.
Page 7
® Tranquility 30 Digital (TE) Series IOM - 60Hz HFC-410A PR EL I MI N ARY R e v. : 3 A u g . , 2 0 1 2 B Horizontal Installation Figure 6a: Typical Closed Loop Horizontal Unit Installation (with Internal Flow Controller) Water 3/8"...
® Tranquility 30 Digital (TE) Series IOM - 60Hz HFC-410A PRE LI MI NA RY R e v. : 3 A u g . , 2 0 1 2 B Horizontal Installation Field Conversion of Air Discharge Figure 7: Left Return Side to Back Overview - Horizontal units can be fi...
® Tranquility 30 Digital (TE) Series IOM - 60Hz HFC-410A PR EL I MI N ARY R e v. : 3 A u g . , 2 0 1 2 B Condensate and Water Connection Condensate Piping Water Connections-Residential (Distributor) Models Pitch the unit toward the drain as shown in Figure 5 to Residential models utilize swivel piping fi...
® Tranquility 30 Digital (TE) Series IOM - 60Hz HFC-410A PRE LI MI NA RY R e v. : 3 A u g . , 2 0 1 2 B vFlow Heat Pump Applications Overview ™ vFlow ™ is a revolutionary new, intelligent, and effi cient way to Figure 11a: Typical Closed-Loop Application (with circulate water (or water plus antifreeze) using INTERNAL, Internal Flow Controller Shown)
® Tranquility 30 Digital (TE) Series IOM - 60Hz HFC-410A PR EL I MI N ARY R e v. : 3 A u g . , 2 0 1 2 B Closed Loop Heat Pump Applications with Internal Flow Controller Units with internal fl...
® Tranquility 30 Digital (TE) Series IOM - 60Hz HFC-410A PRE LI MI NA RY R e v. : 3 A u g . , 2 0 1 2 B Flushing the Earth Loop Once piping is completed between the unit and the ground WARNING! loop, fi...
Page 13
® Tranquility 30 Digital (TE) Series IOM - 60Hz HFC-410A PR EL I MI N ARY R e v. : 3 A u g . , 2 0 1 2 B Flushing the Earth Loop Figure 15b: Valve Position B - Unit Fill / Flush NOTICE: Actual fl...
Page 14
® Tranquility 30 Digital (TE) Series IOM - 60Hz HFC-410A PRE LI MI NA RY R e v. : 3 A u g . , 2 0 1 2 B Flushing the Earth Loop the fl ush cart from the Internal Flow Controller. Install Flow NOTICE: It is recommended to run the unit in the cooling, Controller caps to ensure that any condensation/leakage then heating mode for 15-20 minutes each to ‘temper’...
® Tranquility 30 Digital (TE) Series IOM - 60Hz HFC-410A PR EL I MI N ARY R e v. : 3 A u g . , 2 0 1 2 B Multiple Unit Piping and Flushing Often projects require more than one heat pump. Where circuits for fl...
Page 16
® Tranquility 30 Digital (TE) Series IOM - 60Hz HFC-410A PRE LI MI NA RY R e v. : 3 A u g . , 2 0 1 2 B Multiple Unit Piping and Flushing Figure x: Multiple Units with Internal Flow Controllers Size for Heat Pump Size for ‘A’...
Page 17
® Tranquility 30 Digital (TE) Series IOM - 60Hz HFC-410A PR EL I MI N ARY R e v. : 3 A u g . , 2 0 1 2 B Multiple Unit Piping and Flushing Multiple Units with Internal Modulating Valves and Central Pump This is an application where multiple units are used in conjunction with a central, variable speed pump.
R e v. : 3 A u g . , 2 0 1 2 B Ground Loop Heat Pump Applications Contact your ClimateMaster distributor if you have any Antifreeze Selection - General In areas where minimum entering loop temperatures drop questions as to antifreeze selection.
® Tranquility 30 Digital (TE) Series IOM - 60Hz HFC-410A PR EL I MI N ARY R e v. : 3 A u g . , 2 0 1 2 B Ground Loop Heat Pump Applications 10 gallons [37.9 liters] total. If more than one tankful is Chart 1a: Methanol Specifi...
® Tranquility 30 Digital (TE) Series IOM - 60Hz HFC-410A PRE LI MI NA RY R e v. : 3 A u g . , 2 0 1 2 B Closed Loop - External Central Pumping Applications Figure 17: Typical Closed Loop with Central Pumping Application (with Internal Modulating Motorized Valve Shown) To Thermostat Internal Motorized Modulating Valve...
® Tranquility 30 Digital (TE) Series IOM - 60Hz HFC-410A PR EL I MI N ARY R e v. : 3 A u g . , 2 0 1 2 B Open Loop or Ground-Water Heat Pump Applications Figure 19: Typical Open Loop/Well Application fl...
® Tranquility 30 Digital (TE) Series IOM - 60Hz HFC-410A PRE LI MI NA RY R e v. : 3 A u g . , 2 0 1 2 B Open Loop or Ground-Water Heat Pump Applications The pump should be sized to handle the home’s domestic Water Coil Low Temperature Limit Setting water load (typically 5-9 gpm [23-41 l/m]) plus the fl...
Rev.: 3/22/2012 The ClimateMaster Water Quality Table provides water quality requirements for ClimateMaster coaxial heat exchangers. When water properties are outside of those requirements, an external secondary heat exchanger must be used to isolate the heat pump heat exchanger from the unsuitable water. Failure to do so will void the warranty for the coaxial heat exchanger.
® Tranquility 30 Digital (TE) Series IOM - 60Hz HFC-410A PRE LI MI NA RY R e v. : 3 A u g . , 2 0 1 2 B Hot Water Generator The HWG (Hot Water Generator) or desuperheater option It is always advisable to use water softening equipment on provides considerable operating cost savings by utilizing domestic water systems to reduce the scaling potential and...
Page 25
® Tranquility 30 Digital (TE) Series IOM - 60Hz HFC-410A PR EL I MI N ARY R e v. : 3 A u g . , 2 0 1 2 B Hot Water Generator Figure 22: Anti-Scald Valve Piping Connections Installation ANTI-SCALD The HWG is controlled by two sensors and the DXM2 micro-...
® Tranquility 30 Digital (TE) Series IOM - 60Hz HFC-410A PRE LI MI NA RY R e v. : 3 A u g . , 2 0 1 2 B Hot Water Generator ensure that there is no air remaining in the tank. WARNING! 4.
Be sure the available power is the same voltage and phase shown on the unit serial plate. Line and low voltage wiring must be done in accordance with local codes or the National ® Table 5a: Tranquility 30 (TE) Series Electrical Data Electric Code, whichever is applicable. Compressor...
® Tranquility 30 Digital (TE) Series IOM - 60Hz HFC-410A PRE LI MI NA RY R e v. : 3 A u g . , 2 0 1 2 B Electrical - Low Voltage Wiring Figure 24: Tranquility Low Voltage Field Wiring Table 7: Accessory Relay 2 Confi...
Thermostat DXM2 CAUTION! Board Compressor CAUTION! Refrigerant pressure activated water regulating Compressor Stage 2 valves should never be used with ClimateMaster Auxiliary Heat equipment. Dehumidification Reversing Valve CAUTION! 24Vac Hot 24Vac Common CAUTION! If communicating thermostat is not installed, a Fault LED communicating service tool must be used to confi...
® Tranquility 30 Digital (TE) Series IOM - 60Hz HFC-410A PRE LI MI NA RY R e v. : 3 A u g . , 2 0 1 2 B DXM2 Wiring Diagram with Internal Flow Controller - 96B0005N60 Part 1 of 2 This diagram includes typical wiring details but is not applicable to all units.
Page 31
® Tranquility 30 Digital (TE) Series IOM - 60Hz HFC-410A PR EL I MI N ARY R e v. : 3 A u g . , 2 0 1 2 B DXM2 Wiring Diagram with Internal Flow Controller - 96B0005N60 Part 2 of 2 c l i m a t e m a s t e r.
Page 32
® Tranquility 30 Digital (TE) Series IOM - 60Hz HFC-410A PRE LI MI NA RY R e v. : 3 A u g . , 2 0 1 2 B DXM2 Wiring Diagram with Motorized Modulating Water Valve - 96B0005N62 - Part 1 of 2 This diagram includes typical wiring details but is not applicable to all units.
® Tranquility 30 Digital (TE) Series IOM - 60Hz HFC-410A PR EL I MI N ARY R e v. : 3 A u g . , 2 0 1 2 B DXM2 Wiring Diagram with Motorized Modulating Water Valve - 96B0005N62 - Part 2 of 2 c l i m a t e m a s t e r.
® Tranquility 30 Digital (TE) Series IOM - 60Hz HFC-410A PRE LI MI NA RY R e v. : 3 A u g . , 2 0 1 2 B ECM Blower Control The ECM fan is controlled directly by the DXM2 control board Special Note for AHRI Testing: To achieve rated airfl...
® Tranquility 30 Digital (TE) Series IOM - 60Hz HFC-410A PR EL I MI N ARY R e v. : 3 A u g . , 2 0 1 2 B ECM Blower Performance Data Table 8: Tranquility ® 30 (TE) Series ECM Blower Performance Data Table Airfl...
® Tranquility 30 Digital (TE) Series IOM - 60Hz HFC-410A PRE LI MI NA RY R e v. : 3 A u g . , 2 0 1 2 B DXM2 Controls DXM2 iGate Controller DXM2 is the next generation in DIP Switches –...
® Tranquility 30 Digital (TE) Series IOM - 60Hz HFC-410A PR EL I MI N ARY R e v. : 3 A u g . , 2 0 1 2 B DXM2 Layout and Connections Figure 25: LT1 Limit Setting Low Water Temperature Cutout Selection The DXM2 control allows the fi...
® Tranquility 30 Digital (TE) Series IOM - 60Hz HFC-410A PRE LI MI NA RY R e v. : 3 A u g . , 2 0 1 2 B Unit Commissioning And Operating Conditions Operating Limits Environment – Units are designed for indoor installation only. Never install units in areas subject to freezing or where humidity levels could cause cabinet condensation (such as unconditioned spaces subject to 100% outside air).
® Tranquility 30 Digital (TE) Series IOM - 60Hz HFC-410A PR EL I MI N ARY R e v. : 3 A u g . , 2 0 1 2 B Unit Start-Up and Operating Conditions Miscellaneous: Note any questionable aspects of Unit and System Checkout BEFORE POWERING SYSTEM, please check the following: the installation.
® Tranquility 30 Digital (TE) Series IOM - 60Hz HFC-410A PRE LI MI NA RY R e v. : 3 A u g . , 2 0 1 2 B Unit Start-Up Procedure SERVICE MODE a. Go into Manual Mode activate Y1, and Y2 for Heating.
® Tranquility 30 Digital (TE) Series IOM - 60Hz HFC-410A PR EL I MI N ARY R e v. : 3 A u g . , 2 0 1 2 B Unit Start-Up Procedure If performance during any mode appears abnormal, refer to the DXM2 section or troubleshooting section of this manual.
Page 42
® Tranquility 30 Digital (TE) Series IOM - 60Hz HFC-410A PRE LI MI NA RY R e v. : 3 A u g . , 2 0 1 2 B Unit Operating Conditions - TE Table 14: TE Series Typical Unit Operating Pressures and Temperatures TE026 Full Load Cooling - without HWG active Full Load Heating - without HWG active...
Page 43
® Tranquility 30 Digital (TE) Series IOM - 60Hz HFC-410A PR EL I MI N ARY R e v. : 3 A u g . , 2 0 1 2 B Unit Operating Conditions - TE Table 14: TE Series Typical Unit Operating Pressures and Temperatures: Continued TE064 Full Load Cooling - without HWG active Full Load Heating - without HWG active...
® Tranquility 30 Digital (TE) Series IOM - 60Hz HFC-410A PRE LI MI NA RY R e v. : 3 A u g . , 2 0 1 2 B Table 15a: Performance Data — Tranquility 30 Model 026- Full Load ®...
Page 45
® Tranquility 30 Digital (TE) Series IOM - 60Hz HFC-410A PR EL I MI N ARY R e v. : 3 A u g . , 2 0 1 2 B Table 15b: Performance Data — Tranquility 30 Model 038 - Full Load ®...
Page 46
® Tranquility 30 Digital (TE) Series IOM - 60Hz HFC-410A PRE LI MI NA RY R e v. : 3 A u g . , 2 0 1 2 B Table 15c: Performance Data — Tranquility 30 Model 049 - Full Load ®...
Page 47
® Tranquility 30 Digital (TE) Series IOM - 60Hz HFC-410A PR EL I MI N ARY R e v. : 3 A u g . , 2 0 1 2 B Table 15d: Performance Data — Tranquility 30 Model 064 - Full Load ®...
® Tranquility 30 Digital (TE) Series IOM - 60Hz HFC-410A PRE LI MI NA RY R e v. : 3 A u g . , 2 0 1 2 B Table 15e: Performance Data — Tranquility 30 Model 072 - Full Load ®...
® Tranquility 30 Digital (TE) Series IOM - 60Hz HFC-410A PR EL I MI N ARY R e v. : 3 A u g . , 2 0 1 2 B Preventive Maintenance Water Coil Maintenance three months to minimize the problem. The condensate pan (Direct ground water applications only) - If the system is may also need to be cleaned periodically to insure indoor installed in an area with a known high mineral content...
® Tranquility 30 Digital (TE) Series IOM - 60Hz HFC-410A PRE LI MI NA RY R e v. : 3 A u g . , 2 0 1 2 B Troubleshooting General Table 16: Nominal resistance at various temperatures If operational diffi culties are encountered, perform Resistance Resistance the preliminary checks below before referring to the...
Page 51
® Tranquility 30 Digital (TE) Series IOM - 60Hz HFC-410A PR EL I MI N ARY R e v. : 3 A u g . , 2 0 1 2 B Troubleshooting Outputs values when the lockout occurred. The compressor and reversing valve relays are 24VAC and can be verifi...
® Tranquility 30 Digital (TE) Series IOM - 60Hz HFC-410A PRE LI MI NA RY R e v. : 3 A u g . , 2 0 1 2 B DXM2 Process Flow Chart WARNING! WARNING! HAZARDOUS VOLTAGE! DISCONNECT ALL ELECTRIC POWER INCLUDING REMOTE DISCONNECTS BEFORE SERVICING.
® Tranquility 30 Digital (TE) Series IOM - 60Hz HFC-410A PR EL I MI N ARY R e v. : 3 A u g . , 2 0 1 2 B Functional Troubleshooting Fault Htg Clg Possible Cause Solution Check Line Voltage circuit breaker and disconnect Check for line voltage between L1 and L2 on the contactor Main Power Problems Green status LED off...
® Tranquility 30 Digital (TE) Series IOM - 60Hz HFC-410A PRE LI MI NA RY R e v. : 3 A u g . , 2 0 1 2 B Functional Troubleshooting (cont.) Fault Htg C lg Possible Cause Solution Heating Mode LT2>125°F Check for poor air flow or overcharged unit Unit Performance...
Page 55
® Tranquility 30 Digital (TE) Series IOM - 60Hz HFC-410A PR EL I MI N ARY R e v. : 3 A u g . , 2 0 1 2 B Performance Troubleshooting Symptom Htg Clg Possible Cause Solution Dirty filter Replace or clean Check for dirty air filter and clean or replace Rduced or no air flow...
Page 56
® Tranquility 30 Digital (TE) Series IOM - 60Hz HFC-410A PRE LI MI NA RY R e v. : 3 A u g . , 2 0 1 2 B Performance Troubleshooting (cont.) Symptom Htg Clg Possible Cause Solution Low Dischage Air Too high of air flow Check fan motor speed selection and airflow chart Temperature in Heating...
® Tranquility 30 Digital (TE) Series IOM - 60Hz HFC-410A PR EL I MI N ARY R e v. : 3 A u g . , 2 0 1 2 B Troubleshooting Form Refrigerant Circuit Diagram Customer: Loop Type: Startup Date: Model #: f i t &...
® Tranquility 30 Digital (TE) Series IOM - 60Hz HFC-410A PRE LI MI NA RY R e v. : 3 A u g . , 2 0 1 2 B Warranty G e o t h e r m a l H e a t P u m p S y s t e m s...
Page 59
® Tranquility 30 Digital (TE) Series IOM - 60Hz HFC-410A PR EL I MI N ARY R e v. : 3 A u g . , 2 0 1 2 B Notes c l i m a t e m a s t e r. c o m...
97B0045N04 ClimateMaster works continually to improve its products. As a result, the design and specifi cations of each product at the time for order may be changed without notice and may not be as described herein. Please contact ClimateMaster’s Customer Service Department at 1-405-745-6000 for specifi...
Need help?
Do you have a question about the tranquility 30 and is the answer not in the manual?
Questions and answers
NO COMMUNICATION
When there is no communication in the ClimateMaster Tranquility 30 system, follow these troubleshooting steps:
1. Check Thermostat: Ensure a communicating thermostat is installed. If not, use a communicating service tool for configuration and diagnosis.
2. Verify Connections: Confirm proper wiring between the thermostat and DXM2 control board. Check terminals R, C, and communication wires.
3. Inspect Power Supply: Make sure 24Vac Hot (R) and 24Vac Common (C) are present and supplying correct voltage.
4. Use Diagnostic Tool: If communication is still absent, connect a diagnostic tool to the system for two-way communication and troubleshooting.
5. Check DIP Switch Settings: Verify DXM2 board DIP switch S2-7 is set correctly if dehumidification is used.
6. Review Fault LEDs: Check for any fault indication on LED L or AL1 to help identify communication or system issues.