baltur BTG 15 Instructions For Use Manual page 46

Table of Contents

Advertisement

Available languages

Available languages

The built-in microprocessor controls not only the programming sequence but the information system too.
The individual phases of the programming sequence are displayed as Flash-Code. The following messages can
be distinguished:
Message
waiting for air proving switch
pre-purge
tv1
pre-ignition
tvz
safety time
ts
Delay 2
-stage
nd
running
low mains voltage
Internal fuse defect
> control box defect
Lock-out diagnoses
In case of a failure the LED is permanently illuminated. Every 10 seconds the illumination is interrupted by a fl ash
code, which indicates the cause of the error. Therefore the following sequence is performed which is repeated as
long as the unit is not reset.
Sequence:
illuminated phase
for 10 sec
for 0.6 sec
Error diagnosis
Error message
lock out
safety time
stray light
air proving switch
in closed position
air proving switch
time-out
air proving switch opened
loss of fl ame
Flash-Code for manual lock out
anual/external
lock out
(see also 4. lock out and reset)
ONE STAGE NATURAL GAS BURNERS
Flash-Code
I I .
I I I .
I I I I .
 I .
 I I .
I
I
I
_
_
I  
_
I 
_
dark phase
Flash-Code
I    
Flash-Code
I    
I I   
  I I I
I I I  
I I I I 
    I
         
0006080876 ed 2007/02
Description
I
.
_
_
_
dark phase
for 1.2 sec
Possible fault
within lock out safety time
no fl ame establishment
stray light during monitored phase,
detector may be faulty
air proving switch
contact welded
air proving switch does not
close within specifi ed time
air proving switch opens
during start or operation
loss of fl ame during operation
44 / 87
short pulse
long pulse
short pause
long pause
long pause

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Btg 20Btg 28

Table of Contents