System Configuration Procedures : Multiple System; System Configuration Diagram; Setting The Switches On The Main Unit; Main Circuit - Mitsubishi Electric CAHV-P500YA-HPB Service Handbook

Hot water heat pump
Hide thumbs Also See for CAHV-P500YA-HPB:
Table of Contents

Advertisement

[ II Restrictions ]

(3) System configuration procedures : Multiple system

1. Set the dip switches and rotary switches.
(Switches on the MAIN circuit on the main unit* AND the MAIN and SUB circuits on all sub units on the sub
unit)

System configuration diagram

Unit (MAIN circuit)
External
water
temperature
sensor
Field-supplied dry
contact switch/relay
or remote controller
(PAR-W21MAA)
SW2-8: ON
SW2-9: ON
Address: 1
* The main unit is the unit to which an external water temperature sensor is connected.

Setting the switches on the main unit

MAIN circuit

(1) Set the dip switch SW2-8 to ON. (an external
water temperature sensor) (labeled A in the
figure at right)
(2) Set the dip switch SW2-9 to ON. (multiple unit
control)(labeled A in the figure at right)
SUB circuit
Nothing needs to be changed.
Refer to "Dip switch settings table" (page 63) for
further details.
Make sure the address of the MAIN circuit on the main unit is set to "1" (labeled B in the figure above) and that the
address of the SUB circuit on the main unit is set to "51" (labeled C in the figure above).
The address of each SUB circuit should equal the sum of the MAIN circuit address on the same unit and 50.
Setting the switches on all sub units
MAIN circuit
(1) Set the dip switch SW2-9 to ON. (multiple unit
control) (labeled A in the figure at right)
(2) Set the MAIN circuit addresses with the rotary
switches. (labeled B in the figure at right). Set
the 10's digit with SWU1, and set the 1's digit
with SWU2. Assign sequential addresses to
the MAIN circuit on all sub units starting with 2.
SUB circuit
(3) Set the dip switch SW2-6 to OFF. (power
supply to communication circuit) (labeled C in
the figure at right)
(4) Set the SUB circuit addresses with the rotary switches (labeled D in the figure above). Set the 10's digit with
SWU1, and set the 1's digit with SWU2. Assign sequential addresses to the SUB circuit on all sub units starting with 52.
HWE10060
Unit (SUB circuit)
Unit (MAIN circuit)
PCB
PCB
unit
Main
SW2-9: ON
Address: 51
Address: 2
Unit (SUB circuit)
PCB
PCB
Sub unit
Inter-unit wiring
(M-NET line)
SW2-6: OFF
Address: 52
Main unit (MAIN circuit)
10's digit (0) 1's digit (1)
(0)
B
A
Sub unit (MAIN circuit)
10's digit (0) 1's digit (1)
(0)
B
A
- 21 -
Unit (MAIN circuit)
Unit (SUB circuit)
PCB
PCB
Sub unit
"n"th unit
SW2-9: ON
SW2-6: OFF
Address: 1 + n
Address: 50 + n
Main unit (SUB circuit)
10's digit (5) 1's digit (1)
(0)
C
Sub unit (SUB circuit)
10's digit (5) 1's digit (1)
(0)
D
C
GB

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents