Thermo-On/Off Conditions (Time) - Mitsubishi Electric CAHV-P500YA-HPB Service Handbook

Hot water heat pump
Hide thumbs Also See for CAHV-P500YA-HPB:
Table of Contents

Advertisement

[ VII Control ]
Multiple system control (inlet-water-temperature-based control)
Inlet water temperature
changes
Multiple system control (outlet-water-temperature-based control)
Outlet water temperature
changes

2) Thermo-ON/OFF conditions (time)

Thermo-
Temperature
ON
changes
The unit will stay in operation
of 60 seconds after the unit
went into when the Thermo-ON
conditions were met.
3. When the units are stopped after the water temperature has reached the upper limit setting
DIFF1 = 2 ºC (Initial setting): "1015" Digitally set value
DIFF2 = 2 ºC (Initial setting): "1016" Digitally set value
Tmax (Outside temperature
Individual
system
Built-in
thermistor
Refer to the
section on indi-
External
vidual system.
water
temperature
HWE10060
Thermo-OFF temperature
Preset water temperature
Thermo-OFF temperature
Preset water temperature
Thermo-OFF temperature
Preset water
Thermo-
temperature
OFF
The unit will remain stopped if the anti-short-
cycling protection is in effect.
1.The unit will remain stopped for three minutes
after the unit stopped when the Thermo-OFF
conditions were met.
2.After the compressor stops, it will remain
stopped for 10 minutes.
Refer to section -9- "Anti-short-cycling protection"
(page 84) for detailed information about
anti-short-cycling protection function.
-10 ºC: 65ºC, Outside temperature > -10 ºC : 70ºC)
Control
sensor
method
Inlet-water-
temperature-
based control
Outlet-water-
temperature-
based control
Water tem-
perature con-
trol based on
the external
water temper-
ature reading
When the water temperature is controlled based on the
representative inlet temperature, compressor frequency will
DIFF2/2°C
be controlled as described in section -3-"Compressor
frequency" (page 80). (Automatic operation according to the
DIFF2/2°C
preset temperature)
When the water temperature is controlled based on the
external water temperature sensor reading (outlet water
temperature), compressor frequency will be controlled in the
way that the target water temperature will be maintained.
DIFF2/2°C
The number of units to be in operation will be determined by
DIFF2/2°C
the main unit to maintain the proper operating frequency of
each unit.
When the water temperature is controlled based on the inlet
temperature, compressor frequency will be controlled as
described in section -3- "Compressor frequency" (page 80).
(Automatic operation according to the preset temperature)
Thermo-ON conditions
When SW2-5 (operation restora-
tion after forced stoppage) is set to
ON
Inlet water temperatures are lower
than the "Inlet temperature at
Thermo-OFF DIFF2ºC" AND outlet
temperatures are lower than
"Tmax - DIFF1ºC."
When SW2-5 (operation restora-
tion after forced stoppage) is set to
OFF
Inlet temperatures are lower than
"Tmax - DIFF1ºC" AND outlet tem-
peratures are lower than "Tmax -
DIFF1ºC."
- 91 -
Thermo-OFF
conditions
"External water temperature of
each unit > Tmax" or "Inlet water
temperature of each unit > Tmax"
GB