Notes On Pipe Corrosion; Water Treatment And Water Quality Control; Water Quality Standard - Mitsubishi Electric CAHV-P500YA-HPB Service Handbook

Hot water heat pump
Hide thumbs Also See for CAHV-P500YA-HPB:
Table of Contents

Advertisement

[ II Restrictions ]

2. Notes on pipe corrosion

Water treatment and water quality control

Poor-quality circulating water can cause the water-side heat exchanger to scale up or corrode, reducing heat-
exchange performance. Properly control the quality of the circulating water.
• Removing foreign objects and impurities in the pipes
During installation, keep foreign objects, such as welding and sealant fragments and rust, out of the pipes.
• Water Quality Control
(1) Poor-quality water can corrode or scale up the heat exchanger. Regular water treatment is recommended.
Water circulation systems using open heat storage tanks are particularly prone to corrosion.
When using an open heat storage tank, install a water-to-water heat exchanger, and use a closed-loop circuit
on the air-conditioner side. If a water supply tank is installed, keep contact with air to a minimum, and keep the
level of dissolved oxygen in the water no higher than 1 mg/ℓ.

(2) Water quality standard

Items
pH (25°C)
Electric conductivity
Chloride ion
Sulfate ion
Standard
items
Acid consumption
Total hardness
Calcium hardness
Ionic silica
I
o r
n
Copper
Sulfide ion
Reference
Ammonium ion
items
Residual chlorine
Free carbon dioxide
R
z y
n
r e
s
a t
l i b
Reference: Guideline of Water Quality for Refrigeration and Air Conditioning Equipment. (JRA GL02E-1994)
(3) Please consult with a water quality control specialist about water quality control methods and water quality
calculations before using anti-corrosive solutions for water quality management.
(4) When replacing an air conditioner (including when only the heat exchanger is replaced), first analyze the water
quality and check for possible corrosion.
Corrosion can occur in water systems in which there has been no signs of corrosion. If the water quality level
has dropped, adjust the water quality before replacing the unit.
HWE10060
Lower mid-range temperature water system
Water Temp. ≤ 60ºC
Recirculating water
7
0 .
~
(mS/m) (25 °C)
30 or less
(μs/cm) (25 °C)
[300 or less]
-
50 or less
(mg Cl
/ℓ)
2-
50 or less
(mg SO4
/ℓ)
50 or less
(pH4.8) (mg CaCO
/ℓ)
3
(mg CaCO
/ℓ)
70 or less
3
(mg CaCO
/ℓ)
50 or less
3
(mg SiO
/ℓ)
30 or less
2
(
m
g
F
/ e
ℓ)
1.0 or less
(mg Cu/ℓ)
1.0 or less
2-
/ℓ) Not to be detected Not to be detected Not to be detected Not to be detected
(mg S
+
(mg NH
/ℓ)
0.3 or less
4
(mg Cl/ℓ)
0.25 or less
(mg CO
/ℓ)
0.4 or less
2
y t i
n i
d
e
x
Higher mid-range temperature water system
Make-up water
Recirculating water
8
0 .
7
0 .
~
8
0 .
7
0 .
30 or less
30 or less
[300 or less]
[300 or less]
50 or less
30 or less
50 or less
30 or less
50 or less
50 or less
70 or less
70 or less
50 or less
50 or less
30 or less
30 or less
0.3 or less
1.0 or less
1.0 or less
1.0 or less
0.1 or less
0.1 or less
0.3 or less
0.1 or less
4.0 or less
0.4 or less
- 25 -
Water Temp. > 60ºC
Make-up water
Corrosive
~
8
0 .
7
0 .
~
8
0 .
30 or less
[300 or less]
30 or less
30 or less
50 or less
70 or less
50 or less
30 or less
0.3 or less
1.0 or less
0.1 or less
0.3 or less
4.0 or less
Tendency
Scale-
forming
GB