Mitsubishi Electric CAHV-P500YA-HPB Service Handbook page 85

Hot water heat pump
Hide thumbs Also See for CAHV-P500YA-HPB:
Table of Contents

Advertisement

[ VII Control ]
Step 2
Select the item to be set with
push switch SWP3.
Step 3
Change the values with push
switches SWP1 (↑) or SWP2 (↓).
Select item code 1052 to set the operation temperature (TWL) for the booster heater.
Press push switch SWP3 to select the item code.
Change the values with push switches SWP1 and SWP2.
Until the changed values are saved, the values will blink.
Items that can be set
Booster heater operation
temperature (TWL)
Press and hold push switches SWP1 and SWP2 to fast forward the numbers.
Step 4
Press push switch SWP3 to save
the changed value.
Press SWP3 once within one minute of changing the settings to save the change.
When the new setting is saved, the display will stop blinking and stay lit. The display will, then, return to the item code
display mode.
If SWP3 is not pressed within one minute, the change will not be saved, and the display will return to the item code
display mode.
HWE10060
Item
Initial
Unit
Increm
code
value
ents
1052
10
°C
Setting
Lower
Upper
limit
limit
0.1
0
70
- 78 -
Setting change from
Note
an optional remote
controller
Not possible
GB