11-3. System Configuration Restrictions

11-3-1. Common restrictions for the CITY MULTI system
For each Heat source unit, the maximum connectable quantity of Indoor unit is specified at its Specifications table.
A) 1 Group of Indoor units can have 1-16 Indoor units;
B) Maximum 2 remote controllers for 1 Group;
*MA/ME remote controllers cannot be present together in 1group.
*To wire PAC-YT53CRAU, use a wire with a diameter of 0.3 mm
C) 1 LOSSNAY unit can interlock maximum 16 Indoor units; 1 Indoor unit can interlock only 1 LOSSNAY unit.
D) Maximum 3 System controllers are connectable when connecting to TB3 of the Heat source unit.
E) Maximum 6 System controllers are connectable when connecting to TB7 of the Heat source unit, if the transmission
power is supplied by the Heat source unit.
F) 4 System controllers or more are connectable when connecting to TB7 of the Heat source unit, if the transmission
power is supplied by the power supply unit PAC-SC51KUA. Details refer to 2-3-3-C.
*System controller connected as described in D) and E) would have a risk that the failure of connected Heat source
unit would stop power supply to the System controller
11-3-2. Ensuring proper communication power for M-NET
In order to ensure proper communication among Heat source unit, Indoor unit, LOSSNAY and Controllers, the transmission
power situation for the M-NET should be observed. In some cases, Transmission booster should be used. Taking the power
consumption index of Indoor unit sized P06-P54 as 1, the equivalent power consumption index and supply capability index
of others are listed at Table 11-3-1 and Table 11-3-2.
Indoor unit
Sized
Sized
PEFY-AF1200
P06-P54
P72, 96
CFMR
1
7
2
Centralized
Remote controller
AE-200A
AG-150A-A
TC-24B
EW-50A LMAP04U-E
AE-50A
EB-50GU-A
0
0.5
4
*RC: Remote Controller
Transmission Booster
Power supply unit Expansion controller
PAC-SF46EPA
PAC-SC51KUA
25
5
*If PAC-SC51KUA is used to supply power at TB7 side, no power supply need from Heat source unit at TB7, Connector TB3 itself will therefore have 32.
*1 AE-200A/AE-50A has a built-in function to supply power to the M-NET transmission line. The amount of power that an AE-200A or an AE-50A can supply is
equivalent to the power required by an MN converter (CMS-MNG-E) that is used for maintenance.
With the equivalent power consumption values in Table 11-3-1 and Table 11-3-2, PAC-SF46EPA can be designed into the air-
conditioner system to ensure proper system communication according to 11-3-2-A, B, C.
11-3-2-A) Firstly, count from TB3 at TB3 side the total quantity of Indoor units, ME remote controller, and System controllers.
If the total quantity reaches 40, a PAC-SF46EPA should be set. In this case, Indoor units sized P72 and 96 are
counted as 2 indoor units, but MA remote controller(s) and PZ-41SLB are NOT counted.
11-3-2-B) Secondly, count from TB7 side to TB3 side the total transmission power consumption index. If the total power consumption
reaches 32, a PAC-SF46EPA should be set. Yet, if a PAC-SC51KUA or another controller with a built-in power supply,
such as PAC-YG50ECA, is used to supply power at TB7 side, count from index TB3 side only.
11-3-2-C) Thirdly, count from TB7 at TB7 side the total transmission power consumption index, If the total power consumption reaches
6, a PAC-SF46EPA should be set.
System example
TB7
TB7
Heat source unit
M-NET
Centralized controller
(AG-150A-A)
24VDC
Power supply unit
PAC-SC51KUA
Transmission booster (No.2) should be used,
if the total equivalent transmission power consumption reaches 5.
© 2017 Mitsubishi Electric US, Inc.
Table 11-3-1 The equivalent power consumption
BC
LOSSNAY
controller
LGH-RX-E
CMB
P36NMU-E-BU
P36NMU-E-AU
0
2
6
ON/OFF
MN Converter
controller
PAC-YT40ANRA
CMS-MNG-E
BAC-HD150
0
0
1
Table 11-3-2 The equivalent power supply
BM ADAPTER
PAC-YG50ECA
BAC-HD150
AE-200A/AE-50A
6
6
TB3
01
02
ME remote
controller
TB3
N1
Transmission booster (No.1) should be used,
if the total quantity of Indoor units and ME remote controllers
reaches 40, (Indoor units sized P72 and 96 are counted as 2);
or if the total equivalent transmission power consumption reaches 32.
LOSSNAY
unit
CENTRALIZED CONTROLLER AG-150A
LOSSNAY
remote controller
N3
PQRY-P-T(S)LMU, Y(S)LMU (April 2017 Ver2)
[AWG22]
2
PWFY
MA RC.
PAC-YT53CRAU
P72NMU-E-AU
PAR-FA32MA
PZ-41SLB
PZ-60DR-E
1
5
0
M-NET
Heat source unit
Interface/Converter
MAC-333
TB7 power consumption
PAC-SF83MA-E
2
0
0
System Controller
Heat source unit
EW-50A
Connector TB3 and TB7 total *
0
1.5
32
*1
UP
MODEL
TRANSMISSION BOOSTER
PAC-SF46EPA
POWER RATING
WEIGHT
220-240V:0.7A ~/N
3.4kg
50
MADE IN JAPAN
Transmission
booster
(No.1)
Within N2, conditions 1,2 should be followed.
1.The total quantity of Indoor units and ME remote controller
should not exceed 40.
*Indoor units sized P72 and 96 are counted as 2 units.
2.The total equivalent transmission power consumption
should not exceed 25.
UP
MODEL
TRANSMISSION BOOSTER
PAC-SF46EPA
POWER RATING
220-240V:0.7A ~/N
3.4kg
50
WEIGHT
MADE IN JAPAN
Transmission
booster
LOSSNAY
unit
PAC-SF46EPA
(No.2)
LOSSNAY
remote controller
N4
Within N4, the total equivalent transmission
power consumption should not exceed 25.
ME Remote controller/Adapter
PZ-52SF
PAR-U01MEDU
PAC-YG60MCA
PAC-IF01AHC-J
PAC-YG66DCA
PAC-YG63MCA
0.25
0.5
Heat source unit
Heat source unit
(except TLMU)
TLMU
Connector TB7 only
Connector TB7 only
6
0
ME remote
controller
N2
WR2-123

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents