[ VII Control ]

(1) Setting procedures

Set the dip switches on the circuit board as follows before making the settings for the items described in this section.
Step 0
Set the ON/OFF
switch (SWS1) to
OFF.
Step 1
Set the dip switches
SW2 and SW3.
Step 2
Select the desired
item with the push
switch SWP3.
Step 3
Press the push
switches SWP1 (↑)
or SWP2 (↓) to
increase or
decrease the value.
Step 4
Press the push
switch SWP3 to
save the change.
HWE10060
Set SWS1 to OFF from the remote controller or with the local switch.
Most settings (other than item codes 11 and 13 (water temperature setting)) cannot be
changed unless the ON/OFF setting is set to OFF. *
* Settings can be changed from the optional remote controller, regardless of the ON/OFF status of the operation switch.
SW2
SW3
-10
5
6
7
OFF
OFF
OFF
OFF
Item codes 11, 13, 22, 23, 24, and 25 relate to water-temperature setting.
Press the push switch SWP3 to select an item code.
Press the push switches SWP1 and SWP2 to change the value of the selected item.
The value will keep blinking while it is being changed.

Settings table

Items that can be set
Water temp. setting A
(Heating mode)
Water temp. setting B
(Hot water mode)
Heating Eco mode/
Water temp. setting C1 *3
Heating Eco mode/
Outside temp. setting C2 *3
Heating Eco mode/
Water temp. setting C3 *3
Heating Eco mode/
Outside temp. settingC4 *3
* The graph below shows the relationship between C1/C3 and C2/C4.
Water temp.
setting
Heating Eco
Water temp.
setting C1
Heating Eco
Water temp.
setting C3
Heating Eco
Outside temp.
setting C2
*1 These items need not be set when only a single water temperature setting is used.
When a signal through a dry contact is used to switch between the three modes, the water temperature setting is selected as
follows.
*2 The setting ranges for the water temperature setting A, B, C1, and C3 are shown in the table below.
Water-temperature control
Outlet-water-temperature-based control
Inlet-water-temperature-based control
* When the outside temperature is -5ºC or below and the water temperature is set as follows, the unit may operate at a higher
preset temperature than the preset temperature: Outlet temperature 35ºC/Inlet temperature 30ºC.
Press SWP3 once within one minute of changing the setting with SWP1 or SWP2 to save the
setting.
Once the new setting is saved, the display will stop blinking and stay lit. The display will, then,
return to the item code display mode.
If SWP3 is not pressed within one minute, the change will not be saved and the display will
return to the item code display mode.
8
9
10
OFF
ON
OFF
Item
Initial
Unit
code
value
Increments
11
60
°C
0.1°C
13
65
°C
0.1°C
22
60
°C
0.1°C
23
0
°C
0.1°C
24
35
°C
0.1°C
25
25
°C
0.1°C
Water temp.
setting
Heating Eco
Water temp.
setting C1
Heating Eco
Water temp.
setting C3
Outside temp.
Heating Eco
Outside temp.
setting C4
Lower limit
25.0°C
25.0°C
- 67 -
Setting
Setting change from an
optional remote
Notes
Lower
Upper
limit
limit
(PAR-W21MAA)
25
70
25
70
25
70
*1
Not possible
-20
50
*1
Not possible
25
70
*1
Not possible
-20
50
*1
Not possible
* When the values for C2 and C4
are set to the same value.
Upper limit
70.0°C
65.0°C
controller
Possible
Possible
Outside temp.
GB