WARNING: this UPS product conforms to the current electromagnetic compatibility (EMC) regulations
(C2 class). It may cause radio interference in the home environment. The user may have to adopt
supplementary measures.
The manufacturers cannot accept liability for damage caused by wrong connections or by operations other
than those described in this manual.
I
NSTALLATION PROCEDURES
Before connecting the UPS to the Battery box, ensure compliance with the following points:
Install the UPS and the Battery box on a flat, stable surface.
Avoid placing in positions exposed to direct sunlight or hot air
Maintain room temperature between 0°C and 40°C
N.B.: the UPS can operate with an ambient temperature of between 0°C and 40°C. The optimal
operating temperature for the batteries inside the UPS is between 20 and 25°C. If the operational
lifetime of the batteries is an average of 4 years with an ambient temperature of 20°C, this will be
halved if the temperature goes up to 30°C.
The ambient humidity rate must not exceed 90%.
Avoid dusty environments.
Ensure that the UPS and the Battery box are placed with the front and the rear at least 10 cm away
from walls. Do not place objects on top of the ventilation holes in order to allow adequate
ventilation.
I
NSTALLATION
43