Single - Phase Version - Riello 5KVA Installation And Use Manual

Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 36
S
-
INGLE
PHASE VERSION
1. (SINGLE-PHASE CONNECTION 5-6kVA): use 3 cables with cross-section 6 mm
L) for the input, and 3 cables with cross-section 6 mm
2. Connect the wires to the relative terminals, following exactly the instructions given below:
Input line
a - Make sure that the magneto-thermal switch upstream is open.
b - Connect the earth wire to terminal B.
c - Connect the neutral wire to terminal 4.
d - Connect the live wire to terminal 3.
Output line
a - Connect the earth wire to terminal C.
b - Connect the neutral wire to terminal 6.
c - Connect the live wire to terminal 5.
By-pass line
a - Make sure that a jumper is connected between terminals 7 and 8, needed for proper operation of the
UPS.
3. Tighten the terminals well, close the back-pack and secure it with the screws taken out earlier.
A
3
1
2
4
L
N
BATT.
IN
EXP.
2
for the output (EARTH, N and L).
B
C
5
6
7 8
REMOTE
L
N
BYPASS
OUT
U
SE
2
(EARTH, N and
45

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

6,5kva8kva10kva6kva

Table of Contents