Titanium Tube-in-Tube Exchanger
1. Disconnect the plumbing to the chiller at connection unions (removal is counter-clockwise).
2. Allow water to drain completely from the chiller. Expect to see a lot of water drain out at
first, and then a small amount to continue to drain out over a long period.
3. Place an air hose into the pool inlet of the chiller; wrap a clean rag around the hose to form
a temporary seal.
4. Push all water from the water circuit using compressed air no stronger than 50 psig. The
residual water should be forced out of the pool outlet. Allow compressed air to blow into
the chiller inlet for at least 15-20 seconds after the water stops coming out.
5. Repeat process on the outlet side of the chiller.
6. Partially reconnect plumbing connection unions.
7. Winterizing is complete.
8. When ready to use chiller again, hand-tighten connection unions. Reconnect electrical power, and set the
operating mode on the chiller. Activate filter pump.

SECTION 6 - TROUBLESHOOTING

6.1 Fault Codes

A fault code indicates a specific issue or condition that will require action before the equipment can resume
operating.
Please perform the following troubleshooting.
If the issue reoccurs, please contact AquaCal
AquaCal AutoPilot, Inc." on page 1.
WARNING - Failure to heed the following may result in injury or death.
Repairs must not be attempted by untrained or unqualified individuals.
l
The chiller contains refrigerant under high pressure. Repairs to the refrigerant circuit must not be attempted by
l
untrained or unqualified individuals. Service must be performed only by qualified HVAC technicians. Recover
refrigerant before opening the system.
CAUTION - Failure to heed the following may result in equipment damage.
Service by unauthorized personnel will void the chiller warranty.
l
FLO Indicator
ISSUE
Low or no water detected.
RESOLUTION
1. Confirm the filter pump is on.
2. If a multiple-speed filter pump is being used, run at a higher speed to determine if the error persists. Do not
exceed maximum flow rate for your model.
3. Confirm water is not being diverted away from the chiller.
See "Water Flow Rates" on page 4.
l
See "Adjusting Water Flow Using ΔT (Delta-T)" for more information.
l
Page - 21
®
Technical Support. See "Contacting
Titanium
Tube-in-
Tube