CONTROL SYSTEM
13.3
General functions for all models
13.3.1
COMP operation
o For each Mode including POWER OFF & SB, a Min time delay of 3 min before
COMP restarting, excluding DEICING Mode.
o The Min operation time of COMP under different operating conditions is
Fan, Dry, Overflow, Protection modes, or mode change
13.3.2
IFAN operation
o Whenever the IFAN starts from OFF to ON it will start in Low speed for 25 sec and
then will go to ANY speed.
o Min time interval between IFAN speed change in AUTOFAN Mode, is 30 sec.
o Min time interval between IFAN speed change in H/M/L Mode is 1 sec.
o IFAN speed in Heat/Cool Autofan Mode is determined according to the following
table:
2 t 'T t 1
where in Heat Mode:'T = SPT-RT
Note:
1. In Heat Mode, the rules in section 4.0.3 have the higher priority.
2. The table above can be represent by a hysteresis curve which will minimize
the switching of the IFAN relay and will minimize the change in IFAN speed:
IFAN speed
H
M
L
13-6
Operation Mode
Heat, Cool or Auto Modes
'T
'T t 2
1 t 'T
in Cool Mode:'T = RT-SPT
1
Revision Y05-01
CONTENT
Min operation time of
IFAN Speed
HIGH
MED
LOW
2
3
Service Manual - DNG Series
COMP
3 min.
ignored
o
T [
c]