HP HPE XP P9500 Manual page 27

Hide thumbs Also See for HPE XP P9500:
Table of Contents

Advertisement

and exits through the perforations in the rear door. Either the front fans or the rear fans can cool
the chassis by themselves. The racks do not contain fans. Airflow is from front to back.
Table 14 Heat, power, and airflow
Model Number
AV375A P9500 Flash
Module Chassis
AV392A P9500 1.6TB Flash
Module
AV393A P9500 3.2TB Flash
Module
AV400A - P9500 Disk Array
DKC Module-0 Rack
AV400B - P9500 Disk Array
DKC Module-0 Rack
AV401A - P9500 DKC
Module-1 Rack
AV401B - P9500 DKC
Module-1 Rack
AV402A - P9500 DKU Disk
Unit Rack
AV402B - P9500 DKU Disk
Unit Rack
AV411B P9500 Base 2.5in
Drive Chassis
AV412B P9500 Complete
6
2.5in Drive Chassis
AV413A - P9500 Drive
Chassis SAS Switch Kit
AV423A, AV423B - P9500
8-port 2-8 Gbps FC CHA
AV424A, AV424B - P9500
16-port 2-8 Gbps FC CHA
AV425A - P9500 16p 1-4
Gbps SW FICON CHA
AV426A - P9500 16p 1-4
Gbps LW FICON CHA
AV427A, AV427B - P9500
16p 2-8 Gbps SW FICON
CHA
AV428A - P9500 16p 2-8
Gbps LW FICON CHA
AV429A - P9500 8-port 10
Gbps FCoE CHA
AV440A, AV440B - P9500
ProcessorBlade
AV442A - P9500 DKC Hub
Kit
Heat Output (kW)
6
0.600
3
0.017
3
0.017
1
1.88
0.86
1
1.83
0.48
1
1.47
0.0
see note 5
0.57
0.120
0.072
0.072
0.118
0.118
0.072
0.072
0.072
0.19
0.010
Power Consumption (kVA)
6
0.640
3
0.018
3
0.018
1
1.97
0.90
1
1.93
0.50
1
1.54
0.0
see note 5
0.6
0.076
0.076
0.076
0.124
0.076
0.076
0.076
0.076
0.200
0.010
System specifications and requirements
Air Flow (M3/min)
-
-
-
25
-
25
-
27
-
-
-
-
-
-
-
-
-
-
-
-
-
27

Hide quick links:

Advertisement

Table of Contents
loading