Installation - Honeywell vk41 series Handbook

Gas control for combined valve and ignition system
Table of Contents

Advertisement

INSTALLATION

IMPORTANT
IMPORTANT
Take care that installer is a trained experienced
service man.
Turn off gas supply before starting installation.
Disconnect power supply to prevent electrical shock
and/or equipment damage.
Do not remove seals over inlet and outlet until the
device is ready to be installed.
Take care that dirt cannot enter the gas control during
handling.
Mounting position
The gas control can be mounted 0 to 90 degrees in any
direction from the upright position (from the position when the
operators are on top).
Main gas connection
Gas controls with internal thread
• Take care that dirt cannot enter the gas control during
handling.
• Use a sound taper fitting with thread according to ISO 7-1
or a piece of new, properly reamed pipe, free from swarf.
• Do not thread or tighten the pipe or pipe fitting too far (see
table below). Otherwise distortion and malfunction could
result.
Pipe size (inch)
Max. length of pipe thread (mm)
3
/
14
8
1
/
18.6
2
• Apply a moderate amount of good quality thread compound
to the pipe or fitting only, leaving the two end threads bare.
PTFE tape may be used as an alternative.
• Tighten gas control using the right open end wrench. fig. 3
.
• Ensure the gas flows in the same direction as the arrow on
the bottom of the gas control.
Fig. 3.
Gas controls for flange connection
• Insert "O"-ring in the groove of each flange. If necessary
grease "O"-ring slightly to keep it in place.
• Mount gas control between flanges using the four screws
for each flange.
Gas controls with external thread connection
IMPORTANT
IMPORTANT
Fastening torque flat sealing ring only applicable for
type Klingersil C4324
Olives for this application are not supplied by Honey-
well
Torque of olive applications may differ depending on
olive dimensions.
1
With
/
" nut and flat sealing ring for pipe 14 mm ( fig. 4 .)
2
Nut: drawing: ........................................ 45.006.583-005
Flat sealing ring according to DIN 3535-6 with size
∅18 x ∅12 x 1.5 mm
drawing................................................. 45.006.582-002
Fastening torque: maximum 40 Nm
Pipe end construction: see fig.: 7.
1
With
/
" nut and flat sealing ring for pipe 15 mm ( fig. 4 .)
2
Nut: drawing: ........................................ 45.006.583-004
Flat sealing ring according to DIN 3535-6 with size
∅18 x ∅12 x 1.5 mm
drawing................................................. 45.006.582-002
Fastening torque: maximum 40 Nm
Pipe end construction: fig. 8 .
Fig. 4. External thread connection with nut and flat
21
minimum 25 Nm
minimum 25 Nm
sealing ring
EN2R-9004 0606R20-NE