Honeywell vk41 series Handbook page 20

Gas control for combined valve and ignition system
Table of Contents

Advertisement

Oscillation
Maximum oscillation under all circumstances:
Tap sensitivity of outlet pressure set point
For all gases the maximum deviation may be 1 mbar.
Repeatability of outlet pressure set point
For all gases the maximum deviation from set point is:
mbar or
3% of the set point value, whichever is the greatest.
±
Design life
500.000 cycles for safety and main valve operator.
Cycle frequency maximum 100 cycles /hour.
EN2R-9004 0606R20-NE
Total set point shift
0.5 mbar.
Table 14: Total set point shift servo regulator on/off
±
Pressure range
1.5 ... 20
2 ... 37
0.3
5 ... 50
±
)
*
For other versions see the applicable handbook
Temperature sensitivity VK41../81..VE type:
-15 ... 70°C : 4% of flow
20
)
version*
Tolerance
6% of the set point value or 1 mbar
whichever is the greatest
6% of the set point value or 1.5 mbar
whichever is the greatest