Release Protective Control By Temperature Of Indoor Heat Exchanger; Louver Control; Louver Position; Air Direction Adjustment - Carrier 42cvur018-703 Service Manual

Table of Contents

Advertisement

Item
6. Release protective
<In cooling/dry operation>
control by tempera-
(Prevent-freezing control for indoor heat exchanger)
ture of indoor heat
In cooling/dry operation, the sensor of indoor heat
exchanger
exchanger detects evaporation temperature and
controls the compressor speed so that temperature of
the heat exchanger does not exceed the specified
value.
7˚C
6˚C
5˚C
Reduction of compressor speed

7. Louver control

This function controls the air direction of the indoor unit.
• The position is automatically controlled initial setting of
• The set louver position is stored in memory by the
The angle of the louver is indicated as the louver closes
fully is 0°.

1) Louver position

2) Air direction
adjustment
Horizontal
blowing
• Swing operation is performed in width 35°

3) Swing

• If the stop position exceeds either upper or lower limit
Operation flow and applicable data, etc.
Usual cooling capacity control
"storage position" Louver : (Directs downward 37.4°).
microcomputer, and the louver returns to the stored
position when the next operation is performed.
Cooling operation / AUTO (COOL)
Initial setting of "Storage position"
Louver : (Directs downward 37.4°)
Air direction
Inclined
Blowing
blowing
downward
with the stop position as the center.
position, swing operation is performed in width 35° from
the limit which the stop position exceeded.
R
When the value is
in Q zone, the
Q
compressor speed
is kept.
P
Inclined
Horizontal
blowing
blowing
30
FILE NO. SVM-12052
Description
1) When temperature of the indoor
heat exchanger drops below 5°C,
the compressor speed is
reduced. (P zone)
2) When temperature of the indoor
heat exchanger rises in the
range from 6°C to under 7°C, the
compressor speed is kept.
(Q zone)
3) When temperature of the indoor
heat exchanger rises to 7°C or
higher, the capacity control
operation returns to the usual
control in cooling operation.
(R zone)
• The louver position can
be arbitrarily set up by
pressing [FIX] button.
• Swing
When pressing
[SWING] button during
operation, the louver
starts swinging.