<In case of bottom right or bottom left piping>
• After scribing slits of the front panel with a knife
or a making-off pin, cut them with a pair of
nippers or an equivalent tool.
Slit
Fig.
<Left-hand connection with piping>
Bend the connecting pipe so that it is laid within
43 mm above the wall surface.
If the connecting pipe is laid exceeding 43 mm
above the wall surface, the indoor unit may
unstably be set on the wall.
When bending the connecting pipe, make sure to
use a spring bender so as not to crush the pipe.
Refer to the table below for the bending
radius of each connection pipe.
Outer diameter
∅6.35 mm
∅12.70 mm, ∅15.88 mm
To connect the pipe after installation of the
unit (figure)
(To the front flare)
520 mm
Gas side
420 mm
Liquid side
R30 or less (Ø6.35), R50 or less (Ø12.70, Ø15.88)
Use polishing (polyethylene core or the like for bending pipe).
Outward form of indoor unit
Use a screwdriver handle, etc.
Fig. 10-3-19
NOTE :
If the pipe is bent incorrectly, the indoor unit may
unstably be set on the wall.
After passing the connecting pipe through the pipe
hole, connect the connecting pipes to the auxiliary
pipes and wrap the facing tape around them.
10-3-18
Bending radius
30 mm
50 mm
• Bind the auxiliary pipes (two) and connecting
cable with facing tape tightly.
In case of leftward piping and rear-leftward
piping, bind the auxiliary pipes (two) only with
facing tape.
Auxiliary pipes
Installation
plate
• Carefully arrange pipes so that any pipe does not
stick out of the rear plate of the indoor unit.
• Carefully connect the auxiliary pipes and
connecting pipes to one another and cut off the
insulating tape wound on the connecting pipe
to avoid double-taping at the joint, moreover,
seal the joint with the vinyl tape, etc.
• Since dewing results in a machine trouble,
make sure to insulate both connecting
pipes. (Use polyethylene foam as insulating
material.)
• When bending a pipe, be careful not to crush it.
10-3-7. Indoor Unit Fixing
1. Pass the pipe through the hole in the wall and
hook the indoor unit on the installation plate at
the upper hook.
2. Swing the indoor unit to right and left to confirm
that it is firmly hooked on the installation plate.
3. While pressing the indoor unit onto the wall, hook
it at the lower part on the installation plate.
Pull the indoor unit toward you to confirm that it is
firmly hooked on the installation plate.
1
2
Hook
• For detaching the indoor unit from the installation
plate, pull the indoor unit toward you while pushing
its bottom up at the specified parts.
49
FILE NO. SVM-12052
CAUTION
Indoor unit
Connecting
cable
Fig. 10-3-20
Hook here
1 Installation
plate
Push (unhook)
Fig. 10-3-21
Push
Push
Fig. 10-3-22

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

39cvur018-70342cvur022-703

Table of Contents