* Wire size 28-22 AWG (0.08~0.32 mm
Outer diameter not over 4.7 mm,
control wire length 30 m. or less.
5
Tighten fi rmly
Terminal
but not over
Control wire
0.12 N·m (0.01 kgf·m)
Fig. 10-3-10
<For remote controller>
1. Remove cover of remote controller by sliding down
and take it out.
2. If batteries are exist, please take them out. The
combination of using wire controller and batteries may
cause of batteries explosion.
3. Make hole for insert control wire by use screwdriver
break the polyester sheet as shown on figure
4. Insert control wire from rear side of remote controller
as shown on figure
5. Fix control wire which arrange as shown on figure
and
to terminal by provided screws (tighten firmly
10
but not over : 0.25 N·m (0.03 kgf·m).
6. Set control wire through gutter way at rear side of
remote controller as shown on figure
7. Fix provided screw (∅ 3.1 x 16L) on the wall to hang
remote controller as shown on figure
8. Mark and arrange hole for fix below screw
(∅ 3.1 x 25L) as shown on figure
9. Assembly battery cover which provided with accessory
bag then use provide screw (∅ 3.1 x 25L) to fix battery
cover together with wall as shown on figure
(tighten firmly but not over 0.15 N.m (0.02 kgf.m)).
10. Reassembly cover of remote controller.
Polyester sheet close hole
for insert control wire
30 mm
10 mm
* Wire size 28-22 AWG (0.08~0.32 mm
Outer diameter not over 4.7 mm,
control wire length 30 m. or less.
Fig. 10-3-11
70 mm
4
2
)
5 mm
Control wire out position
Control wire
Control wire through out position
.
8
.
11
.
12
.
12
13
7
Control wire
9
2
)
Control wire
Terminal
Tighten fi rmly but not over
0.25 N·m (0.03 kgf·m)
6
Tighten fi rmly but
not over 0.15 N·m
(0.02 kgf·m)
.
7
9
*Remark :
1. Recommend to use double insulation lead wire for
connect remote control and air conditioner.
2. For wire operation, 1 remote control can control only
1 indoor unit.
3. In wire operation, remote controller will return to initial
condition (PRESET, TIMER and CLOCK will return to
initial condition) when user shutdown power supply
of air conditioner.
<How to install the air inlet grille on the indoor unit>
• When attaching the air inlet grille, perform the same
process as for removal but in severse order.
8

10-3-6. Piping and drain hose installation

!
<Piping and drain hose forming>
* Since dewing results in a machine trouble, make
sure to insulate both connecting pipes. (Use
polyethylene foam as insulating material.)
47
FILE NO. SVM-12052
Control wire
Hole for hang
remote controller
Remote controller
Remote controller
"
Battery cover
Screw
Fig. 10-3-12
Control wire
Screw (∅3.1 x 16L) for
hang remote controller
Wall
Screw (∅3.1 x 25L) for
fi x battery cover
#
$