7. CONTINUITY (RESISTANCE) TESTS
WARNING
Ensure that circuits to be tested are not live.
Disconnect the instrument from the circuit under test before operating the function
switch.
To select the low resistance range select 'CONTINUITY'.

7.1 Test Procedure

The object of continuity testing is to measure only the resistance of the parts of the wiring
system under test. This measurement should not include the resistance of any test leads
used. The resistance of the test leads needs to be subtracted from any continuity
measurement. The KEW6016 is provided with a continuity null feature which allows
automatic compensation for any test lead resistance.
You should only use the test leads supplied with the instrument.
Operation of Function Switch
Ω
NULL OFF
ON
Fig.11
Proceed as follows:-
1 Select the continuity test by rotating the Rotary switch.
2 Insert the Test Leads to the L and PE terminal on KEW6016 respectively
as shown in Fig.12.
Red
Green
Fig.12
3 Connect the ends of the test leads firmly together (see Fig.13) and press and lock down the
test button. The value of the lead resistance will be displayed.
F1
Switches on / off NULL function
F2
Switches on / off 2Ω buzzer
F3
N/A
F4
N/A
L terminal
Red cord of Model7188, or
Model7196 Remote Test Lead
PE terminal
Green cord of Model7188
17