PR 9113 Manual page 30

Temperature / ma converter
Hide thumbs Also See for 9113:
Table of Contents

Advertisement

LERBAKKEN 10, 8410 RØNDE DENMARK
Ex input
CH1 (terminal 41,42,43,44)
CH2 (terminal 51,52,53,54)
U
:
8.7 V
o
I
:
18.4 mA
o
P
:
40 mW
o
Lo/Ro
892 μH/
IIC
C
5 F
o.
L
100 mH
o.
U
:
10 V
i
I
:
30 mA
i
C
:
30 nF
i
L
820 nH
i.
Status Relay. terminal (33,34)
Voltage max:
Power max:
Current max:
Zone 2 installation:
Voltage max:
Power max:
Current max:
Installation notes:
Install in pollution degree 2, overvoltage category II as defined in IEC60664-1
Do not separate connectors when energized and an explosive gas mixture is present.
Do not mount or remove modules from the Power Rail when an explosive gas mixture is present.
Disconnect power before servicing.
The wiring of unused terminals is not allowed.
In type of protection [Ex ia Da] the parameters for intrinsic safety for gas group IIB are applicable.
For installation in Zone 2, the module shall be installed in an enclosure in type of protection Ex n or
Ex e, providing a degree of protection of at least IP54. Cable entry devices and blanking elements
shall fulfill the same requirements.
For installation on Power Rail in Zone 2, only Power Rail type 9400 supplied by Power Control Unit
type 9410 (Type Examination Certificate KEMA 07ATEX0152 X) is allowed.
Revision date:
2012-07-04
28
IIB
IIA or I
50 F
1000 F
300 mH
700 mH
Version Revision:
V4 R0
9113 - Product Version 9113-004
125 VAC / 110 VDC
62.5 VA / 32 W
0.5 A AC / 0.3 ADC
32 VAC / 32 VDC
16 VA / 32 W
0.5 A AC / 1 ADC
Prepared by:
PB
9113QI01
Page:
2/3