Mes-
Cause
sage
661
On process screen: recipe setpoint or previous
value configured in recipe: field is neither recipe
setpoint or previous value.
662
Invalid destination configured for return reference
in screen.
663
Data record memory full (during startup)
664
Standard data records for the configured recipes
require more than 20 Kbytes. Unit switches to
COM TEXT mode.
665
Configuration of interfaces incorrect, printer/PLC
interfaces have same physical characteristics.
667
Configuration error:
Variable x:
1
Data type is not DB
2
DB number is greater than 15
3
DB length is greater than 1024
4
DW is in data block header
5
Actual value not in send block
6
Setpoint not in receive block
7
Setpoint/actual value not in receive block
8
Initial value not in send block
9
Data type is not DB
10
DB number is greater than 15
11
DB length is greater than 1024
12
DW is in data block header
13
Area is in wrong DB
14
Sum of data blocks too great
668
Incorrect configuration.
Meaning of variables:
1: Incompatible PLC types configured
2: No PLC configured
3: Incorrect baud rate configured
669
Too many actual values (> 512) have been confi-
gured for cyclic reading in a screen/variable.
670
Too many variables requested simultaneously.
B-14
Remedy:
Change field type or remove field
and retransfer configuration
Change configuration and retransfer.
Configure fewer or smaller recipes.
Check interface parameters.
x = 1..8: Change the configuration of the
process link and retransfer.
x = 9..13:Change configuration of area
pointer and retransfer
x = 14:
Restrict configuration and re-
transfer.
Change configuration and retransfer.
Lengthen standard clock pulse or
configure fewer variables on screen.