Siemens simatic hmi op7 Equipment Manual page 146

Operator panel
Table of Contents

Advertisement

Mes-
Cause
sage
109
Restart after change of operating mode from of-
fline to online.
110,
OP is in "normal" mode.
113
114
PLC has been restarted.
115
Establishment of logical link with PLC in pro-
gress.
117
Connection with PLC is OK again following a
fault.
119
Automatic restart.
120
Restart after change of S5 protocol.
124
Restart following selection of different language.
129
SINEC L1 or SINEC L2 parameter has been
changed
130,
Startup due to loop-through operation when
132
online.
134
Restart due to offline operation.
136
PLC not responding.
138
Data block not available on PLC
201
Hardware fault on timer module.
202
Error reading date
203
Error reading time
204
Error reading day
205
Printer not ready and internal storage of print jobs
is no longer possible.
206
Printer not ready. Print job placed in temporary
storage.
207
Buffer printout or print screen function cancelled.
210
Internal error
OP co-ordination area not receivable during star-
tup.
212
Internal error
Bit for changing operating mode has been inver-
ted erroneously.
213
Offline mode not possible at present.
214
The job number sent by the PLC or configured in
a function field is too large.
B-4
Remedy:
Check program sequence on PLC.
Check physical connection.
Set up relevant memory area.
Send unit for repair.
Send unit for repair.
Send unit for repair.
Send unit for repair.
Make sure printer is ready or disable
message logging.
Make sure printer is ready.
Check printer, cable and connectors.
Press restart button.
Restart OP.
Try change of operating mode again
later.
Check PLC program and configured
screen.
Equipment Manual OP7, OP17
Release 04/99