Mes-
Cause
sage
397
– The part program specified does not exist.
– The record specified does not exist.
– The PLC specified (FM or NC) is not ready.
398
– The command cannot be executed in the MCU
mode selected.
– The command is not supported by the MCU ver-
sion.
399
– The PLC does not have a directory of tool correc-
tions.
– The tool correction specified does not exist.
400
Illegal key pressed.
401
Value entered could not be converted.
402
Operator error on STATUS VAR or FORCE VAR
screen:
403
Incorrect time entered
404
Incorrect date entered
406
Operator error on STATUS VAR or FORCE VAR
screen
407
You have attempted to delete the only data record
for a recipe.
409
Lower limit violated: you have attempted to enter
a setpoint that is below the configured lower li-
mit.
410
Upper limit violated: you have attempted to enter
a setpoint that is above the configured upper li-
mit.
411
Illegal screen selection because incorrect PLC
type specified (external driver)
500...
Scheduler, counter, date or time data can not be
503
sent.
504
Free ASCII Protocol: operator input value could
not be sent.
505
The data record can not be sent as the recipe disa-
ble bit on the PLC is set or because transfer of a
recipe is still in progress.
506
Overload: too many message blocks with the
same block number in transit.
B-8
Remedy:
only 10 entries are permitted (after
pressing INS if 10th line already
used).
Values can only be changed after up-
date operation has been cancelled
(BREAK key).
Enter a value that is greater than or
equal to the specified value. No limit
is indicated for data of the type
DOUBLE.
Enter a value that is less than or
equal to the specified value. No limit
is indicated for data of the type
DOUBLE.
Change configured interface
parameter.
This error can occur if the PLC is
temporarily overloaded or if the
p
y
function block is not invoked for
f
i
bl k i
i
more than 1.5 s.
Try sending again later when the
PLC has released the recipe mailbox.
This error occurs if the PLC sends
too many jobs using 'collect message
area' within a certain period of time.
Equipment Manual OP7, OP17