Troubleshooting Chart; Diagnostic Chart - Rheem 96v series Installation Instructions Manual

4 position condensing two-stage, communicating gas furnaces w/ecm blower
Table of Contents

Advertisement

2-STAGE COMMUNICATING INTEGRATED
FURNACE CONTROL (IFC)

DIAGNOSTIC CHART

Be sure to note dip switch settings before troubleshooting.
1) For communicating systems, Remove communications
connections from the T-stat (E1, E2) and use a jumper wire
between W1 & R also between R & W2 to set high stage gas
heat. For legacy systems ensure W2 & W1 are properly
connected and make sure both are energized w/ 240 AC after
the heat call is placed.
2) Set FAN switch to "AUTO" on T-stat.
3) Set thermostat to call for heat (set temp. differential to greater
than 10°F). (Comm. jumper W1 to R and W2 to R)
4) "H" should be displayed at "SSD's" and should be on steady, if
flashing check dip switches (Item "1").
Does the IDM Start on Low Speed?
IS
"A capital H is displayed at IFC SSD'S" ?
Lower case "h"
(pre-purge) IDM runs for 30 sec. at low speed?
Spark Electrodes (SE) Energize?
ECM BLOWER "ON" DELAY
Does ECM blower start on high heat
speed 15-20 seconds after burners light?
CHECK:
AIRFLOW - ensure no restrictions, such as dirty filter, blower wheel,
dampers or closed registers, Etc. exist.
LIMITS - ensure good wire and connections between I.F.C. and all limits.
makes sure limits are not open when circulating air temperature is within a
specific range.
ROLLOUTS - Ensure rollouts or overtemperature limits do not need to be
reset. make sure no flame rollout in burner compartment due to blocked flue
or heat exchanger or combustion restriction.
OVERFIRE - ensure furnace is not overfired (temp rise is above stated
range). Check gas valve, proper orifice size, gas presure
Remove the 2nd stage heat call while low heat call
remains. Ensure 24 VAC to W1 & 0 VAC to W2
Continued on next page.
ECM = Constant CFM Blowers. (Electronically commutated motor)
TSTAT = Thermostat.
IDM = Induced Draft Motor (or Inducer).
IFC = Integrated Furnace Control (or control board).
PS = Pressure Switch(es).
PFC = Power Factor Correction Choke.
SE = Spark Electrode (s).
SSD = Seven Segment Display of Furnace control
COMM. = Communication.
I&O = Installation & Operation Instructions Manual.
Dual SSD'S "ON" ?
Is thermostat heat call present?
For 24 VAC (Non-Comm. T-stat., is 24 VAC on W1 and/or W2 of
IFC. H or h should be displayed at SSD'S. ?
Is a fault code displayed at IFC?
(After 10 Sec. a fault code will display anyway)
H or h only
For 1st 10 Sec. only
-Check line voltage at I.D.M.
-Check Wires And connections between I.D.M. and I.F.C.
-Ensure line voltage between P3, Pin 2 & P3, Pin 3 of I.F.C. (High IND Output).
-Check I.D.M. Capacitor.
Check t-stat, replace if
necessary.
Check W2 & connections,
replace or repair as
necessary
Does IDM Run for 60 Sec. and then off
for five minutes with fault
45, 46 or 57 displayed?
See I&O.
PROBLEM
G0 T0
PERSISTS ?
Does gas valve remain
energized?
I
- Check all connections between I.F.C. & E.C.M. Motor.
- Check 24v to E.C.M. control (4pin connector, pin 1-4)
- Check Dip switch setting.
- Check P.F.C. choke. (if present)
- Check all wiring and connections to P.F.C choke.
- Check fault code display, see "fault codes" in I & O. (if present)
- Check line voltage to motor (115VAC).
Note: IFC SSD's will display "22 or 33".
FAULT
Under "Troubleshooting"
in I & O Manual
- See FAULT CODES under "Troubleshooting" in
I&O Manual.
P2 - 6
NOTE: If IFC goes into lockout, shut off main power to unit, wait 30
seconds then reset power or removed heat call and re-establish.
?
Note: If good flame is not sensed a fault code
"11" or "13" will be displayed at SSD's
Note: "12" is low flame sense, furnace should
still operate well.
CHECK:
-Grounding on I.F.C. in place and continuity between screw and field
-installed ground.
-Flame sense rod clean (clean if nessessary).
-Wire continunity between flame sense rod and Pin P2-7 on I.F.C.
-Flame carries across all burners, and all burners stay lit.
CHECK:
- Fault codes at IFC SSD - see FAULT CODES under troubleshooting
in I&O manual.
- 24V Between IFC pins P2-5 & P2-4 of I.F.C.
- Make sure heat call present at T-stat.
- T-stat wires and connections
DISCONNECT POWER BEFORE SERVICING.
SERVICE MUST BE BY A TRAINED,
QUALIFIED SERVICE TECHNICIAN.
P2 - 4 on IFC.
Fault code
"45", "46" or
"57" displayed
at SSD's.
121

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

96mdv series

Table of Contents