Carrier 50TJ016-028 Installation, Start-Up And Service Instructions Manual page 22

Single-package rooftop units 50 hz
Table of Contents

Advertisement

AIRFLOW
50
(L/s)
r/s
BkW kW
r/s
2595
11.4 1.49 1.68 12.7 1.71 1.92 13.9 1.94 2.18 15.0 2.17 2.44 16.1 2.41 2.71 17.1 2.66 2.99 18.1 2.91 3.28 19.0 3.17 3.57
2833
12.2 1.76 2.01 13.4 1.99 2.26 14.5 2.21 2.52 15.6 2.45 2.78 16.6 2.69 3.06 17.6 2.94 3.34 18.5 3.19 3.62 19.4 3.45 3.92
3069
13.0 2.09 2.37 14.1 2.31 2.63 15.2 2.55 2.89 16.2 2.78 3.16 17.2 3.03 3.44 18.1 3.28 3.72 19.0 3.53 4.01 19.9 3.79 4.30
3305
13.8 2.45 2.78 14.9 2.68 3.04 15.9 2.91 3.31 16.8 3.15 3.58 17.8 3.40 3.86 18.7 3.65 4.15 19.6 3.91 4.44 20.4 4.16 4.73
3541
14.6 2.84 3.23 15.6 3.07 3.49 16.6 3.31 3.77 17.5 3.56 4.04 18.4 3.81 4.33 19.3 4.06 4.61 20.1 4.32 4.91 20.9 4.58 5.20
3777
15.5 3.27 3.72 16.4 3.51 3.99 17.3 3.75 4.26 18.2 4.00 4.54 19.1 4.25 4.83 19.9 4.51 5.12 20.7 4.77 5.41 21.5 5.03 5.71
4013
16.3 3.74 4.24 17.2 3.98 4.52 18.1 4.22 4.80 18.9 4.48 5.09 19.7 4.73 5.38 20.5 4.99 5.67 21.3 5.25 5.97 22.1 5.52 6.27
4249
17.2 4.24 4.82 18.0 4.49 5.10 18.9 4.74 5.38 19.7 4.99 5.67 20.4 5.25 5.96 21.2 5.51 6.26 21.9 5.77 6.56 22.7 6.04 6.86
4485
18.0 4.78 5.43 18.8 5.03 5.72 19.6 5.29 6.01 20.4 5.54 6.30 21.2 5.80 6.60 21.9 6.07 6.90 22.6 6.33 7.20 23.3 6.60 7.51
4721
18.9 5.36 6.09 19.7 5.62 6.38 20.4 5.87 6.68 21.2 6.13 6.97 21.9 6.40 7.27 22.6 6.67 7.57 23.3 6.93 7.88 24.0 7.21 8.19
AVAILABLE EXTERNAL STATIC PRESSURE (Pa)
AIRFLOW
448
(L/s)
r/s
BkW kW
r/s
2595
20.0 3.43 3.86 20.4 3.57 4.02 20.8 3.71 4.17
2833
20.3 3.71 4.21 20.8 3.84 4.36 21.2 3.97 4.52
3069
20.7 4.05 4.60 21.2 4.18 4.75 21.6 4.32 4.91
3305
21.2 4.43 5.03 21.6 4.56 5.18 22.0 4.70 5.34
3541
21.7 4.84 5.50 22.1 4.98 5.66 22.5 5.11 5.81
3777
22.2 5.30 6.02 22.6 5.43 6.17 23.0 5.57 6.32
4013
22.8 5.78 6.57 23.2 5.92 6.73 23.5 6.06 6.88
4249
23.4 6.31 7.17 23.7 6.45 7.33 24.1 6.59 7.48
4485
24.0 6.88 7.82 24.3 7.02 7.97 24.7 7.15 8.13
4721
24.6 7.48 8.50
LEGEND
BkW
— Brake Kilowatts
FIOP
— Factory-Installed Option
kW
— Input Kilowatts to Motor
*Standard drive range for Low-Medium static drive on 50TJ024 is 12.8 to
15.2 r/s. Standard drive range for High static drive on 50TJ024 is 16.6 to
20.3 r/s. Other r/s require a field-supplied drive.
NOTES:
1. Maximum continuous bkW is 7.68. The maximum continuous watts is 8640.
Do not adjust motor rpm such that motor maximum bkW and/or kW is
exceeded at the maximum operating L/s.
AIRFLOW
50
(L/s)
r/s
BkW
kW
3305
14.1
2.41
2.00
3541
14.9
2.82
2.35
3777
15.8
3.28
2.73
4013
16.7
3.78
3.15
4249
17.6
4.33
3.60
4485
18.4
4.92
4.10
4721
19.3
5.56
4.63
4957
20.2
6.25
5.21
5193
21.1
6.99
5.82
5311
21.5
7.38
6.15
AIRFLOW
(L/s)
399
r/s
BkW
3305
20.7
4.34
3541
21.2
4.80
3777
21.8
5.30
4013
22.4
5.84
4249
23.0
6.42
4485
23.7
7.06
4721
24.4
7.74
4957
25.1
8.47
5193
25.8
9.25
5311
LEGEND
BkW
— Brake Kilowatts
FIOP
— Factory-Installed Option
kW
— Input Kilowatts to Motor
*Standard drive range for Low-Medium static drive on 50TJ028 is 14.8 to
17.8 r/s. Standard drive range for High static drive on 50TJ028 is 18.6 to
22.4 r/s. Other r/s require a field-supplied drive.
NOTES:
1. Maximum continuous bkW is 9.92 (400 v) or 8.60 (220 v). The maximum
continuous watts is 11,000 (400 v) or 9,600 (220 v). Do not adjust motor
rpm such that motor maximum bkW and/or kW is exceeded at the maxi-
mum operating L/s.
Table 10 — Fan Performance Data (SI) — 50TJ024* (70.3 kW)
AVAILABLE EXTERNAL STATIC PRESSURE (Pa)
100
149
BkW kW
r/s
BkW kW
473
498
BkW kW
r/s
BkW kW
Table 11 — Fan Performance Data (SI) — 50TJ028* (87.9 kW)
AVAILABLE EXTERNAL STATIC PRESSURE (Pa)
100
149
r/s
BkW
kW
r/s
BkW
15.1
2.67
2.22
16.2
2.93
15.9
3.09
2.57
16.9
3.36
16.7
3.55
2.96
17.7
3.83
17.6
4.06
3.38
18.4
4.34
18.4
4.61
3.84
19.2
4.90
19.2
5.21
4.34
20.0
5.51
20.1
5.86
4.88
20.8
6.16
20.9
6.56
5.46
21.7
6.87
21.8
7.30
6.08
22.5
7.62
22.2
7.69
6.41
22.9
8.01
AVAILABLE EXTERNAL
STATIC PRESSURE (Pa)
448
kW
r/s
BkW
3.62
21.5
3.63
4.00
22.0
4.11
4.41
22.5
4.63
4.86
23.1
5.20
5.35
23.7
5.81
5.88
24.4
6.47
6.45
25.0
7.18
7.06
25.7
7.94
7.71
199
249
r/s
BkW kW
r/s
BkW kW
2. Static pressure losses (i.e., EconoMi$er) must be added to external static
pressure before entering fan performance table.
3. Interpolation is permissible. Do not extrapolate.
4. Fan performance is based on wet coils, clean filters, and casing loses. See
Table 16A for accessory/FIOP static pressure information.
5. Extensive motor and drive testing on these units ensures that the full brake
kilowatt and kW range of the motor can be utilized with confidence. Using
your fan motors up to the kW or bkW rating shown will not result in nui-
sance tripping or premature motor failure. Unit warranty will not be affected.
6. Use of a field-supplied motor may affect wiring size. Contact your Carrier
representative for details. For additional information on motor performance,
refer to Evaporator-Fan Motor Performance Table 19.
199
kW
r/s
BkW
kW
r/s
2.44
17.1
3.20
2.66
18.1
2.79
17.8
3.63
3.02
18.7
3.19
18.5
4.11
3.42
19.4
3.62
19.3
4.63
3.86
20.1
4.08
20.0
5.20
4.33
20.8
4.59
20.8
5.81
4.84
21.5
5.13
21.6
6.47
5.39
22.3
5.72
22.4
7.18
5.98
23.1
6.34
23.2
7.94
6.61
23.8
6.67
23.6
8.34
6.94
24.2
kW
3.87
4.25
4.67
5.12
5.62
6.15
6.72
7.33
2. Static pressure losses (i.e., EconoMi$er) must be added to external static
pressure before entering fan performance table.
3. Interpolation is permissible. Do not extrapolate.
4. Fan performance is based on wet coils, clean filters, and casing loses. See
Table 16A for accessory/FIOP static pressure information.
5. Extensive motor and drive testing on these units ensures that the full brake
kilowatt and kW range of the motor can be utilized with confidence. Using
your fan motors up to the kW or bkW rating shown will not result in nui-
sance tripping or premature motor failure. Unit warranty will not be affected.
6. Use of a field-supplied motor may affect wiring size. Contact your Carrier
representative for details. For additional information on motor performance,
refer to Evaporator-Fan Motor Performance Table 19.
22
299
349
r/s
BkW kW
r/s
BkW kW
249
299
BkW
kW
r/s
BkW
kW
3.48
2.89
19.0
3.76
3.13
3.92
3.26
19.6
4.20
3.50
4.40
3.66
20.2
4.69
3.91
4.93
4.10
20.9
5.22
4.35
5.50
4.58
21.6
5.80
4.83
6.12
5.09
22.3
6.43
5.35
6.78
5.65
23.0
7.10
5.91
7.50
6.24
23.7
7.82
6.51
8.26
6.88
24.5
8.59
7.15
8.66
7.21
24.9
8.99
7.49
399
r/s
BkW kW
349
r/s
BkW
kW
19.8
4.05
3.37
20.4
4.50
3.75
21.0
4.99
4.16
21.6
5.53
4.60
22.3
6.11
5.09
23.0
6.74
5.61
23.7
7.42
6.18
24.4
8.14
6.78
25.1
8.92
7.43
25.5
9.32
7.77