Omron E5CN Manual page 44

Digital temperature controller with 11-segment display
Hide thumbs Also See for E5CN:
Table of Contents

Advertisement

Vari-
Ad-
able
Parameter name
dress
type
C1
0000
Operation/adjustment
protect
C1
0001
Initial setting/commu-
nications protect
C1
0002
Setup change protec-
tion
C1
0003
Set point
C1
0004
Alarm value 1
C1
0005
Upper-limit alarm 1
C1
0006
Lower-limit alarm 1
C1
0007
Alarm value 2
C1
0008
Upper-limit alarm 2
C1
0009
Lower-limit alarm 2
C1
000A
Alarm value 3
(See note 2.)
C1
000B
Upper-limit alarm
value 3 (See note 2.)
C1
000C
Lower-limit alarm
value 3 (See note 2.)
3.1 Variable Area (Setting Range) List
Setting (monitor) value
H'00000000 (0): No restrictions in operation and adjust-
ment levels
H'00000001 (1): Move to adjustment level is prohibited.
H'00000002 (2): Display and change of only "PV" and
"PV/SP" parameters is allowed.
H'00000003 (3): Display of only "PV" and "PV/SP" param-
eters is allowed.
H'00000000 (0): Move to initial setting/communications
setting level is allowed. (Move to
advanced function setting level is dis-
played.)
H'00000001 (1): Move to initial setting/communications
setting level is allowed. (Move to
advanced function setting level is not dis-
played.)
H'00000002 (2): Move to initial setting/communications
setting level is prohibited.
H'00000000 (0): OFF (Changing of setup on Controller
display is allowed.)
H'00000001 (1): ON (Changing of setup on Controller dis-
play is prohibited.)
SP lower limit to SP upper limit
H'FFFFF831 to H'0000270F (−1999 to 9999)
H'FFFFF831 to H'0000270F (−1999 to 9999)
H'FFFFF831 to H'0000270F (−1999 to 9999)
H'FFFFF831 to H'0000270F (−1999 to 9999)
H'FFFFF831 to H'0000270F (−1999 to 9999)
H'FFFFF831 to H'0000270F (−1999 to 9999)
H'FFFFF831 to H'0000270F (−1999 to 9999)
H'FFFFF831 to H'0000270F (−1999 to 9999)
H'FFFFF831 to H'0000270F (−1999 to 9999)
Level
Protect
Operating
3-3

Advertisement

Table of Contents
loading

Table of Contents