Control system for scroll chillers cgan/cxan 209-214 cgcl 200-600 cgwh/ccuh 115-250 cgwn/ccun 205-215 raul 190-800
Hide thumbs Also See for Tracer CH530:

Advertisement

High Evaporator
Chiller
Water Temperature
High Pressure
Circuit
Cutout
Emergency Stop
Chiller
Outdoor Air Temp
Chiller
Sensor
MP: Non-Volatile
None
Memory
Reformatted
Check Clock
Platform
MP: Could not Store
Platform
Starts and Hours
MP: Non-Volatile
Platform
Block Test Error
Starts/Hours
Cprsr
Modified
32
Diagnostics
Immediate
NonLatch
Immediate
Latch
Immediate
Latch
Warning and
Latch
Special Action
Warning
Latch
Warning
Latch
Warning
Latch
Warning
Latch
Warning
NonLatch
All
The evaporator leaving water temperature is above 46°C. This
diagnostic shall clear once the evaporator leaving water temperature
falls below 43.3°C. This diagnostic protects the rupture disk. The
evaporator water pump shall not run when this diagnostic is active.
All
The high pressure cutout switch was open for more than one
second.
All
Emergency Stop input is open.
All
Bad Sensor or LLID. If configured as an air-cooled this diagnostic
shall use a minimum low refrigerant temperature ignore time of
30 seconds.
All
MP has determined there was an error in a sector of the Non-Volatile
memory and it was reformatted. Check settings.
All
The real time clock had detected loss of its oscillator at some time in
the past. Check / replace battery? This diagnostic can be effectively
cleared only by writing a new value to the chillers time clock using
the TechView or DynaViews set chiller time functions.
All
MP has determined there was an error with the previous power
down store. Starts and Hours may have been lost for the last
24 hours.
All
MP has determined there was an error with a block in the Non-
Volatile memory. Check settings.
All
A counter for compressor starts or hours has been modified by
TechView. This diagnostic is immediately and automatically cleared
and thus can only be seen in the historic diagnostic list.
Local
Local
Local
Remote
Remote
Remote
Remote
NA