Download Print this page

Trane Tracer CH530 User Manual page 12

Control system for scroll chillers cgan/cxan 209-214 cgcl 200-600 cgwh/ccuh 115-250 cgwn/ccun 205-215 raul 190-800
Hide thumbs Also See for Tracer CH530:

Advertisement

12
DynaView Interface
The chilled water reset status area
in the most right column will
display one of the following
messages
Return
Constant Return
Outdoor
Disabled
The left column text "Front Panel",
"BAS", "External", "Auxiliary",
"Chilled Water Reset", and "Active
Chilled Water Setpoint" will always
be present regardless of installation
or enabling those optional items. In
the second column, "-----" will be
shown if that option is Not Installed.
Otherwise the current setpoint from
that source will be shown.
Setpoints that are adjustable from
the DynaView (Front Panel chilled
water setpoint, Auxiliary chilled
water setpoint) will provide
navigation to their respective
setpoint change screen via a
double-arrow to the right of the
setpoint source text. The setpoint
change screen will look identical to
the one provided in the Chiller
Setpoints screen. The "Back" button
on the setpoint change screen
provides navigation back to the
setpoint arbitration screen.
The "Back" button on the setpoint
arbitration screen provides
navigation back to the chiller screen.
Other Active Setpoints
The Active Hot Water Setpoint will
behave the same way as the Active
Chilled Water Setpoint, with the
exception that Hot Water does not
have an Auxiliary source. Front
Panel Hot Water Setpoint will
provide navigation to its setpoint
change screen.
The Active Demand Limit Setpoint
will behave the same way as the
Active Chilled Water Setpoint,
except that its units are % and there
is an Ice Building source in place of
the Auxiliary source. Front Panel
Demand Limit Setpoint will provide
navigation to its setpoint change
screen.
The Active Ice Termination Setpoint
will behave the same way as the
Active Chilled Water Setpoint, with
the exception that Ice Termination
does not have an external or
auxiliary source.
CG-SVU02E-GB