24
DynaView Interface
External/BAS Feature Settings (subscreen of Feature Settings)
Description
1. Ext Chilled/Hot Water Setpoint
2. Ext Demand Limit Setpoint
3. Maximum Capacity Debounce Time
4. Limit Annunc Debounce Time
5. LCI-C Diag Encoding
6. LCI-C Diag Language
Chilled Water Reset Feature Settings (subscreen of Feature Settings)
Description
1. Chilled Water Reset
2. Return Reset Ratio
3. Return Start Reset
4. Return Maximum Reset
5. Outdoor Reset Ratio
6. Outdoor Start Reset
7 . Outdoor Maximum Reset
Air Temperature Reset Feature Settings (subscreen of Feature Settings)
Description
8. Air Temperature Reset
9. Return Reset Ratio
10. Return Start Reset
11. Return Maximum Reset
12. Outdoor Reset Ratio
13. Outdoor Start Reset
14. Outdoor Maximum Reset
Evap Freeze Protection - Pumps Feature Settings (subscreen of Feature Settings)
Description
1. Evaporator Freeze Avoidance:
2. Evap Freeze Avoid Time Const:
3. Evap Freeze Avoid Time Const:
4. Evap Freeze Avoidance Margin:
Resolution or (Enumerations),
Default
(Enable, Disable), Disable
(Enable, Disable), Disable
30 seconds
30 seconds
(Text, Code) Text
(English, Selection 2, Selection 3)
English (0)
Resolution or (Enumerations),
Default
(Const Return, Outdoor, Return,
Disable), Disable
XXX
XXX.X
XXX.X
XXX
XXX.X
XXX.X
Resolution or (Enumerations),
Default
(Const Return, Outdoor, Return,
Disable), Disable
XXX
XXX.X
XXX.X
XXX
XXX.X
XXX.X
Resolution or (Enumerations),
Default
(Enable, Disable), Enable
(Fixed, Adaptive), Adaptive
XX.X
XXX.X
Units
Enum
Enum
Seconds
(MM:SS)
Seconds
(MM:SS)
Enum
Enum
Units
Enum
Percent
Temperature
Temperature
Percent
Temperature
Temperature
Units
Enum
Percent
Temperature
Temperature
Percent
Temperature
Temperature
Units
Enum
Enum
Minutes
Temperature
CG-SVU02E-GB